Irreversible Physical Damage
The casing is severely charred, cracked, or deformed; internal components are exposed; and there is a distinct odor of burnt plastic.
Coil pins or main circuit terminals are completely ablated or broken, making repair via rewiring impossible.
Internal mechanical structures are jammed, the iron core is seized by rust, or springs are broken or deformed; the unit cannot be restored to operational precision even after disassembly.
Complete Failure of Electrical Parameters
Measured coil resistance is 0Ω (short circuit) or infinite (open circuit); the relay fails to actuate when powered, and standard maintenance cannot fix it.
Contacts are severely ablated or welded shut; the normally open terminal remains conductive after power-off, preventing the circuit from breaking; or contacts are worn down to two-thirds of their original thickness, rendering them incapable of conducting electricity.
During operation, the voltage drop across the contacts exceeds 0.5V, and contact resistance far exceeds standard values; normal performance cannot be restored even after cleaning or sanding the contacts.
Insulation resistance between contacts or between contacts and the coil tests below 10MΩ using a 500V megohmmeter, failing to meet safety requirements.
Complete Failure of Protection Functions
The relay fails to actuate when the rated operating voltage is applied, or fails to release when power is cut to the coil, resulting in a complete breakdown of protection logic.
Actuation and release voltages deviate significantly from the nominal range on the nameplate; even after repeated verification with a relay protection tester, the operating error exceeds ±20%, failing to meet system setting requirements.
For smart relays, internal chip damage causes a total loss of communication; protection parameters cannot be modified, data sampling fails, and restoring factory settings proves ineffective.