NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of overcurrent protection of transformer nr-310h/v in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Introduction
The NR-310H/V is a microcomputer-based protection and monitoring relay designed for overcurrent protection of transformer circuits in small-current grounding systems rated 10kV and below. Installed on the incoming or outgoing side of a transformer, it acts as the back-up protection against phase-to-phase short circuits, ground faults and overloads, and trips the breaker before the fault spreads to the transformer and the rest of the switchgear.
The relay does not replace differential protection. It covers the overcurrent layer that every transformer circuit needs, and it is built to cope with transformer-specific conditions: magnetizing inrush blocking prevents false trips at energization, three inverse-time curves let you coordinate with upstream and downstream devices, and non-electric quantity inputs let transformer body signals trip or alarm through the same relay.
It is used on distribution transformers, dry-type transformers, oil-immersed transformers, station service transformers and box-type (pad-mounted) substations. The NR-310H/V is available in standard and customized configurations. The series also includes NR-311H/V (dual-incoming protection and auto-switching), NR-312H/V (section-switch protection and auto-switching) and NR-313H/V (PT cabinet monitoring and protection group), and comes in horizontal (H) and vertical (V) enclosure formats to fit different panel layouts.

Key Features & Protection Functions
-

Transformer Overcurrent Protection
- Three-section overcurrent protection with directional and composite-voltage blocking
-
Magnetizing inrush blocking to avoid false trips when the transformer is energized
-
Inverse time-limit overcurrent with three selectable curves: standard inverse, very inverse and extremely inverse
-
Overload protection (alarm or trip)
-
Negative-sequence overcurrent protection
-
High-current trip blocking
-
Overcurrent post-acceleration
-

Ground Fault & Voltage Protection
- Three-section zero-sequence overcurrent protection
-
Zero-sequence inverse time-limit overcurrent
-
Zero-sequence overcurrent post-acceleration
-
Over/low-voltage protection (alarm or trip)
-
Zero-sequence overvoltage (alarm or trip)
Transformer Body Signals
- Non-electric quantity protection: transformer gas, temperature and pressure-relief signals can be connected to trip or alarm
-
10-way digital input (customizable) and 4-way digital output (dry contacts)
-

Measurement & Communication
-
3-phase + I0 current protection/measurement channel
-
3-phase + U0 voltage measurement channel
-
RS-485 port with Modbus, IEC 60870-5-101 and IEC 60870-5-103 protocols
Reclosing is also available on the platform for feeder applications, but it is normally not used on transformer circuits.
-
Technical Specifications
|
Parameter |
Specification |
|
Applicable Scope |
Small-current grounding systems, 10kV and below; overcurrent protection of transformer incoming/outgoing circuits |
|
Rated Voltage |
100V |
|
Rated Frequency |
50Hz |
|
Rated Current |
5A, 1A (customized) |
|
Auxiliary Power Supply |
AC/DC 85V–265V; DC 48V; DC 24V |
|
Current Protection/Measurement Channel |
3-phase + I0 |
|
Voltage Measurement Channel |
3-phase + U0 |
|
Overcurrent Protection |
Three-section, with directional and composite-voltage blocking |
|
Inverse-Time Curves |
3 curves (standard, very, extremely inverse) |
|
Inrush Blocking |
Yes |
|
Non-Electric Quantity Protection |
Yes |
|
Digital Input |
10-way (customizable) |
|
Digital Output |
4-way dry contacts |
|
Communication Port |
RS-485 |
|
Communication Protocol |
Modbus / 101 / 103 |
|
Operating Temperature |
-30℃ ~ +55℃ |
|
Relative Humidity |
≤95%, non-condensing |
|
Atmospheric Pressure |
80–110kPa |
|
Test Standard Atmospheric Condition |
15℃–35℃, 45%–75% RH, 86–106kPa |
|
Dimensions (NR-310H) |
157mm (W) × 74mm (H) × 110mm (D) |
|
Panel Cutout (NR-310H) |
146 ± 0.2mm (W) × 69.8 ± 0.2mm (H) |
|
Dimensions (NR-310V) |
74mm (W) × 157mm (H) × 110mm (D) |
|
Panel Cutout (NR-310V) |
69.8 ± 0.2mm (W) × 146 ± 0.2mm (H) |
|
Compliance |
Type-tested at KETOP Laboratory; IEC-TC95 international standard testing |
Environment: the surrounding air must be free of conductive, corrosive or explosive substances, and the installation site must be protected from rain and snow.
Applications

Transformer incoming cabinets (10kV side)
- Back-up overcurrent and ground-fault protection at the incoming side of distribution, dry-type, oil-immersed and box-type transformers.

Industrial distribution transformer circuits
- Protection of transformer circuits in mines, steel plants and chemical plants, where load changes are frequent and short-circuit protection must stay selective.

Station service and distribution transformer circuits
- Overcurrent and overload protection for station service transformers and distribution transformers in substations and distribution rooms.
How It Works
Signal Acquisition
Three-phase currents, zero-sequence current and voltage signals are sampled from the CT and PT circuits of the transformer.
Protection Logic
The microprocessor compares the signals with the set overcurrent, zero-sequence and voltage thresholds. Inrush blocking recognizes magnetizing inrush at energization.
Fault Judgment
For a real fault, the relay decides the trip stage according to the definite-time or selected inverse-time curve. Non-electric signals from the transformer body are processed in parallel.
Trip And Report
The relay issues the trip command through its dry-contact outputs and reports status over RS-485 (Modbus/101/103) to your SCADA.
Why Choose NAHO: Custom Engineering Capability

Built Around Your Project, Not Our Catalog
- 30+ years of power automation experience. Our history goes back to 1992, and we have delivered custom solutions for 144+ projects from 110kV down to 10kV, across more than 11 provinces in substations, mines, steel plants, chemical plants and photovoltaic projects.
-
Customizable on the NR-310H/V. Digital input channels are user-definable. Rated current can be customized to 5A or 1A to match your CT. Horizontal (H) or vertical (V) installation fits your panel layout.
-
OEM/ODM, project integration, technical support and after-sales service.
-
Custom enclosure and panel design for volume orders. Tooling investment is justified once your order volume supports it.
-
Tested before it ships. Each unit goes through SMT with AOI inspection, a 72-hour burn-in on 24V/48V/220V power, withstand-voltage and short-circuit testing, and a final factory inspection.
Certifications & Standards




- Type-tested at the National Relay Protection & Automation Equipment Quality Inspection and Testing Center (KETOP Laboratory)
- Passed IEC-TC95 international standard testing
- Contributor to the drafting of national and energy-industry standards, including NB/T 11054-2023 (anti-islanding protection), NB/T 11483-2024 (relay protection for urban rail AC power supply) and NB/T 11480-2024 (outdoor control cabinet environment control for smart substations)
- State Grid qualified supplier
- National High-Tech Enterprise; National "Specialized, Refined, Distinctive and Innovative" enterprise
- 70+ patents and software copyrights
Case Studies / Project References

Featured projects
- Power supply protection and distribution for the opening ceremony of the 16th Asian Games (Haixinsha Square, 2010)
- Three Gorges Yunyang reservoir area project
Selected references (project names withheld, pending permission)
|
Industry |
Voltage Level |
Region |
|
Cement plant substation |
110kV |
Gansu |
|
Coking plant waste-heat power generation |
66kV |
Shanxi |
|
Gold mine distribution room renovation |
66kV |
Jilin |
|
Aluminum manufacturing |
35kV |
Shandong |
|
Chemical plant substation |
35kV |
Shandong |
|
Iron ore mine substation |
35kV |
Hebei |
|
Data center distribution room |
35kV |
Inner Mongolia |
|
Tobacco logistics center |
35kV |
Guizhou |
|
Coal mine substation |
35kV/6kV |
Shanxi |
|
Distributed PV project (15.6MW) |
35kV |
Zhejiang |
|
Textile factory substation |
35kV |
Xinjiang |
|
Coal mine substation |
10kV |
Sichuan |
FAQ
Q1: What is overcurrent protection of a transformer?
It is the protection that detects short-circuit and overload currents flowing through a transformer circuit and trips the breaker. It is used as back-up protection on the incoming or outgoing side of the transformer.
Q2: Where is the NR-310H/V used?
On incoming and outgoing circuits of distribution, dry-type, oil-immersed, station service and box-type transformers in 10kV and below small-current grounding systems.
Q3: Does the NR-310H/V replace transformer differential protection?
No. It provides overcurrent back-up protection. Differential protection is a separate function.
Q4: How does it handle transformer inrush current?
It has magnetizing inrush blocking, which prevents false trips when the transformer is energized.
Q5: What protection functions does the NR-310H/V provide?
Three-section overcurrent with directional and composite-voltage blocking, negative-sequence overcurrent, inverse time-limit overcurrent, overload, three-section zero-sequence overcurrent, over/low-voltage and zero-sequence overvoltage protection, plus non-electric quantity protection.
Q6: Which inverse-time curves are supported?
Three curves: standard inverse, very inverse and extremely inverse.
Q7: Can transformer gas, temperature or pressure-relief signals be connected?
Yes. The non-electric quantity protection accepts transformer body signals for trip or alarm.
Q8: Can the digital I/O or rated current be customized?
Yes. Digital input channels can be user-defined, and rated current can be customized
Q9: Do you provide OEM/ODM customization?
Yes. We offer OEM/ODM, project integration, technical support and after-sales service. Custom enclosures are available for volume orders.
Q10: What is the warranty?
Two years, counted from the delivery date.
Q11: Can you provide technical drawings, wiring diagrams and testing support?
Yes. Send us your project details and we will provide the documents and technical support you need.
Get a Quote

Send us the following and we will reply within 24 hours:
- Project name and location
- System voltage and frequency
- Transformer type (distribution / dry-type / oil-immersed / station service / box-type)
- Protected side (incoming or outgoing)
- Required protection functions
- Communication protocol needs
- Quantity
- Customization requirements (digital I/O, rated current, H/V format, enclosure)
Hot Tags: overcurrent protection of transformer nr-310h/v, China overcurrent protection of transformer nr-310h/v manufacturers, suppliers, factory