Transformer Management and Protection Relay NR-500T

Transformer Management and Protection Relay NR-500T

Factory-built relay for station service and distribution transformer protection, measurement and switch control, up to 110kV.
Made by NAHO, a power automation manufacturer since 1992.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of transformer management and protection relay nr-500t in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

NH32-2

 

The NR-500T is a microcomputer-based transformer management and protection relay, designed and manufactured in our own factory in Yueqing, Zhejiang, China. It is built for protection, measurement and switch control of station service transformers, workshop power transformers, distribution transformers and grounding transformers in systems rated 110kV and below, with arc-suppression coil grounding or ungrounded neutrals.

In one unit, the NR-500T combines current and voltage protection, zero-sequence protection, non-electrical protection (temperature, gas and protective-fence signals) and an operation box with trip, close and anti-pumping logic. It can be installed centrally in a relay panel or locally in the switchgear cabinet, and fully supports substation and distribution-room integrated automation systems.

 

Beyond the standard configuration, the NR-500T is available with customized rated current, rated voltage and communication options, so it fits your project instead of forcing your project to fit the relay.

product-1265-949

 

 

Key Features & Protection Functions

 

  • product-1200-800

    Protection Functions

    • Current instantaneous (quick-break) protection (ANSI 50)

    • Time-limited quick-break protection

    • Overcurrent protection (ANSI 51)

    • Overload protection

    • High-voltage side zero-sequence overcurrent, three-stage (ANSI 50N/51N)

    • Low-voltage side zero-sequence overcurrent

    • Overvoltage protection (ANSI 59)

    • Undervoltage protection (ANSI 27)

    • Zero-sequence overvoltage protection (ANSI 59N)

  • product-5712-4284

    Non-Electrical Protection Functions

    • Abnormal temperature alarm
    • Light gas alarm

    • Over-temperature trip

    • Heavy gas trip (ANSI 63)

    • Protective fence open trip

     

    Measurement Functions

    • 3-phase protection current + 3-phase measurement current + I0H + I0L

    • 3-phase voltage + U0

  • product-1265-949

    Communication Functions

    • 1 × RS-485 port as standard

    • Optional: 2 × RS-485, or 2 × Ethernet

     

    Control & Monitoring Functions

    • Operation box: trip, close with self-hold, and anti-pumping

    • 16 digital inputs; 14 digital outputs

    • PT disconnection self-check

    • CT disconnection self-check

    • Operation-circuit self-check

    • Fault recording

 

 

Technical Specifications

 

Parameter

Specification

Applicable Scope

Systems rated 110kV and below, arc-suppression coil grounded or ungrounded; protection, measurement and switch control of station service, workshop power, distribution and grounding transformers

Current Channels

3-phase protection + 3-phase measurement + I0H + I0L

Voltage Channels

3-phase + U0

Auxiliary Power Supply

AC/DC 110V or AC/DC 220V; DC 48V

Rated Voltage

100V; 400V (customized)

Rated Frequency

50Hz

Rated Current

5A; 1A (customized)

Digital Input

16-way

Digital Output

14-way

Communication Port

1 × RS-485 standard; optional 2 × RS-485 or 2 × Ethernet

Operation Box

Trip, close with self-hold, anti-pumping

Operating Temperature

-30°C ~ +55°C

Relative Humidity

≤95%, non-condensing

Atmospheric Pressure

80–110kPa

Test Standard Atmospheric Condition

+15°C ~ +35°C, 45%–75% RH, 86–106kPa

Installation Environment

Air free of conductive dust, acidic/alkaline corrosive or explosive substances; lightning, rain and snow protection in place

Dimensions

156mm (W) × 232mm (H) × 198mm (D); body depth 171mm

Panel Cutout

138mm (W) × 212mm (H)

Compliance

Type-tested at the KETOP Laboratory (National Relay Protection & Automation Equipment Quality Inspection Center); IEC-TC95 international standard tested

 

Applications

 

 

modular-1
  • Station service transformers: Protection and control of the power supply for substation and plant auxiliary loads.

  • Workshop power transformers: Protection of transformers feeding workshop and production-line power in industrial, mining, steel and chemical sites.

modular-2
  • Distribution transformers: Protection, measurement and switch control in distribution rooms.

  • Grounding transformers: Protection in arc-suppression coil grounded or ungrounded systems, using the I0H, I0L and U0 channels.

modular-3
  • Integrated automation: Panel-mounted centrally or installed locally in switchgear, supporting substation and distribution-room automation systems.

 

 

How It Works

 

Signal Acquisition

3-phase current, I0H, I0L, 3-phase voltage and U0 are sampled, together with the temperature, gas and fence signals.

Protection Logic

The microprocessor compares the values with set thresholds for overcurrent, zero-sequence, voltage and non-electrical conditions.

Fault Judgement

PT and CT disconnection self-checks confirm that the signals are valid before action is taken.

Trip Command And Recording

The operation box issues the trip with anti-pumping logic, and fault recording stores the event.

 

 

Why Choose NAHO: Built Around Your Project, Not Our Catalog

product-1267-1027

We are the factory, not a trading intermediary. That matters when your transformer project does not fit a standard box.

 

  • 30+ years of power automation experience. Our roots go back to 1992, and we have customized solutions for 144+ different projects.

  • Verifiable custom points on NR-500T: rated current (5A or 1A), rated voltage (100V or 400V), auxiliary supply (AC/DC 110V, AC/DC 220V or DC 48V) and communication (2 × RS-485 or 2 × Ethernet).

  • Enclosure and panel customization. Custom enclosures require tooling investment, so we accept them for large-volume orders.

  • OEM/ODM, project integration, technical support and after-sales service, all from one manufacturer.

  • Proven range. Projects span 110kV, 66kV, 35kV and 10kV, across 11+ provinces, including substations, mines and a 10.96606MW distributed PV project.

  • In-house production control: SMT with AOI inspection, wave soldering, 72-hour aging, withstand-voltage and short-circuit testing, then factory inspection before shipment.

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711
  • Type tests at the KETOP Laboratory (National Relay Protection & Automation Equipment Quality Inspection Center)
  • IEC-TC95 international standard testing
  • Drafting participant in national and energy-industry standards, including the 35kV-and-below relay protection national standard (2019 and 2021), NB/T 11054-2023, NB/T 11483-2024 and NB/T 11480-2024
  • State Grid qualified supplier (since 2018)
  • National high-tech enterprise; National "Specialized, Refined, Distinctive and Innovative" enterprise (2023)
  • 70+ patents and software copyrights

 

Case Studies / Project References

 

 

Project

Voltage Level

Industry

Shandong Jinan Longshan Relay Pumping Station user substation

35kV

Water / utility

Shanxi Datong Xing'er Gou Coal Mine substation

35kV/6kV

Mining

Jilin Yanji central heating plant, 66kV–6kV distribution

66kV–6kV

Heating / utility

Liaoning Yingkou Deyuan Carbon Plant

66kV

Industrial

Gansu Zhangye Shandan Tieqi Cement substation

110kV

Building materials

Zhejiang Yongjia 35kV user substation (toy production base)

35kV

Manufacturing

Inner Mongolia Baotou Furong substation expansion

35kV

Power

Anda Wastewater Treatment Plant distribution room

10kV

Environmental

Shanghai Hudong Heavy Machinery 35kV–6.3kV distribution

35kV–6.3kV

Heavy industry

Qinghai Golmud Salt Lake 35kV substation

35kV

Chemical

 

Featured: the power-supply protection and distribution project for the opening ceremony of the 16th Asian Games (2010, Haixinsha Square) and the Three Gorges Yunyang reservoir project.

 

 

FAQ

 

Q1: What is a transformer management and protection relay?

A microprocessor-based device that protects a transformer against faults and abnormal conditions, while also providing measurement and switch control.

Q2: Where is the NR-500T used?

In systems rated 110kV and below, to protect station service, workshop power, distribution and grounding transformers.

Q3: Can it be used in arc-suppression coil grounded or ungrounded systems?

Yes. The NR-500T is designed for both, with I0H, I0L and U0 channels for zero-sequence protection.

Q4: What protection functions does it provide?

Current quick-break, time-limited quick-break, overcurrent, overload, three-stage high-voltage side zero-sequence overcurrent, low-voltage side zero-sequence overcurrent, overvoltage, undervoltage and zero-sequence overvoltage.

Q5: Does it handle transformer non-electrical signals?

Yes. It covers abnormal temperature alarm, light gas alarm, over-temperature trip, heavy gas trip and protective fence open trip.

Q6: Can rated current, voltage or communication be customized?

Yes. Rated current can be 5A or 1A, rated voltage 100V or 400V, and communication can include 2 × RS-485 or 2 × Ethernet.

Q7: Can it be installed in the switchgear cabinet?

Yes. It can be panel-mounted centrally or installed locally in the switchgear.

Q8: What do I need to provide for a quote?

See the checklist below.

Q9: Do you provide OEM/ODM customization, and what is the MOQ?

Yes, we offer OEM/ODM and enclosure customization for large-volume orders. The MOQ for the NR-500T is 10 units.

Q10: Can you provide technical drawings, wiring diagrams and testing support?

Yes. We provide technical support and after-sales service, and our warranty is 2 years from arrival.

 

Get a Quote 

 

product-1269-952

Reply from NAHO within 24 hours. Please send:

  • Project name & location
  • System voltage, frequency and grounding method (arc-suppression coil or ungrounded)
  • Transformer type (station service / workshop / distribution / grounding)
  • Required protection functions, including non-electrical signals
  • Communication needs (RS-485 / Ethernet)
  • Quantity
  • Customization requirements

 

Request a Quote

 

Hot Tags: transformer management and protection relay nr-500t, China transformer management and protection relay nr-500t manufacturers, suppliers, factory