Wiring And Commissioning Of Protection Relays

Sep 11, 2026 Leave a message

Standard Wiring Procedures
1. Main Circuit (Power Circuit) Wiring
For three-phase protection relays, connect the main input terminals (L1/L2/L3 or 1/3/5) in series with the load-side terminals of the AC contactor's main contacts. Connect the output terminals (T1/T2/T3 or 2/4/6) directly to the motor's three-phase terminals, ensuring the full motor current flows through the relay's thermal elements.
For earth leakage/phase sequence protection relays: Connect the three-phase lines (L1/L2/L3) to the detection terminals (1/2/3) and connect the yellow-green grounding wire separately to the ground busbar; strictly avoid connecting it to the neutral wire.
When wiring, select conductors matched to the motor's rated current and tighten terminal screws securely to prevent excessive contact resistance, which could cause overheating.


2. Control Circuit Wiring
Core Rule: Connect the relay's normally closed (NC) auxiliary contact (terminals 95-96) in series within the contactor coil's control circuit; in the event of an overload, this cuts off power to the coil, thereby stopping the motor for protection.
The normally open (NO) auxiliary contact (terminals 97-98) can be connected to an external fault alarm light or signal circuit to output an alarm signal when protection is triggered.
For phase sequence protection relays, connect the normally closed (NC) contact (terminals 5-6) directly in series with the motor's self-locking control circuit; this cuts off the control power supply immediately if a phase sequence error or phase loss occurs.