Safety-Related Precautions
Before maintenance, completely disconnect both the main power and control power supplies, display a "Do Not Switch On" warning sign, and verify that the circuit is de-energized; disassembling a relay while it is live is strictly prohibited.
Wear insulating gloves; avoid touching contacts and pins with bare hands to prevent contamination from sweat or damage to internal electronic components caused by electrostatic discharge.
When performing live operational testing, use insulated tools and ensure a two-person monitoring arrangement to prevent electric shock or accidental equipment activation/deactivation.
Cleaning-Related Precautions
Use low-pressure (0.2 MPa) dry compressed air for cleaning; do not use high-pressure air streams, as this could deform precision components such as springs or thin contacts.
Use anhydrous isopropyl alcohol or specialized electronic contact cleaner for cleaning contacts; do not use gasoline or strong acid/alkali solvents, which could corrode the contact plating.
If polishing oxidized contacts, use only fine-grit metallographic sandpaper (1500 grit or higher) and apply light, unidirectional strokes; do not use coarse sandpaper or files with heavy pressure, as excessive wear could reduce the contact surface area.