Tool Preparation
Prepare the following in advance: multimeter, 1500-grit fine metallographic sandpaper, electronic contact cleaner, anhydrous isopropyl alcohol, soft-bristled brush, low-pressure (0.2 MPa) dry compressed air, torque screwdriver, and insulating gloves.
Visual and Wiring Inspection
Inspect the housing for cracks, scorch marks, or signs of water ingress/moisture; discard and replace the unit immediately if the housing shows signs of ablation.
Tighten all terminals using a torque screwdriver: apply 0.8–1.2 N·m for small control relays and 1.5–2.5 N·m for high-current relays.
Wipe oxidized terminals with contact cleaner and apply a thin layer of conductive paste after they dry completely; replace the socket base entirely if there is severe rust.
Clean the control cabinet's ventilation filters to ensure unobstructed airflow for relay heat dissipation.
Deep Cleaning Procedures
Use low-pressure (0.2 MPa) compressed air to blow dust and metal debris from the iron core, armature, and contact gaps; do not use high-pressure air, as it may deform springs or thin contacts.
For contacts with slight blackening or oxidation: wipe repeatedly with a lint-free cotton swab dipped in anhydrous isopropyl alcohol and allow to air dry.
For contacts with slight ablation or carbon buildup: lightly sand once or twice in a single direction using 1500-grit metallographic sandpaper, then thoroughly clean away any residual grit using alcohol.
If contacts show pitting, sticking/welding, or a reduction in thickness by half: replace immediately with an identical OEM relay; do not attempt to repair or reuse them.