NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of motor overload protection relay nr-624 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

NR-624 Motor Overload Protection Relay for Motor Feeders up to 10kV

 

 

NH15-2

 

Why Motors Burn Out Before Anyone Notices

Motors are seldom lost to one dramatic fault. They die from repeated heavy starts, a rotor that stalls under load, currents drifting out of balance, or a damaged supply circuit. A motor overload protection relay exists to catch these slow problems early. The NR-624 is a microcomputer relay in the NR-620 series, built for small-current grounding systems rated 10kV and below, and it combines overload alarm or trip, inverse-time overcurrent, locked-rotor protection and start-up supervision in one compact case.

What Pushes a Motor Into Overload

Clogged impellers, seized bearings, slipping belts, sagging line voltage and blocked ventilation all drag winding current above nameplate value, and heat accumulates faster than most operators expect. Catching that drift early means a warning at the console instead of a rewind at the repair shop, and fewer unplanned stoppages on conveyors, kilns, mixers and similar lines.

 

Built in Our Own Workshop

NAHO is the factory, not a reseller. Our manufacturing history dates to 1992, when the predecessor Dachang Electric opened in Yueqing's Liushi electrical hub. Today we design, program, assemble, age and test every NR-624 ourselves in Yueqing, Zhejiang, and we can supply it in a standard configuration or adapted in digital inputs, rated current and appearance.

Choosing the Right NR-620 Series Model

  • Motor feeder: NR-624
  • Incoming and outgoing feeder: NR-620
  • Two incoming supplies and bus coupler: NR-622
  • PT cabinet watching and paralleling two PT sets: NR-623
  • PT cabinet watching and protecting one PT set: NR-623A
product-1200-900

 

 

 

What the NR-624 Gives You

  • product-1200-800

    Protection

    • Overload, with a choice of alarm or trip
    • Inverse-time overcurrent and three-step overcurrent with voltage and direction blocking (50/51)
    • Negative-sequence overcurrent (46) for unbalanced supply

    • Three-step zero-sequence overcurrent (50N/51N) for earth faults

    • Over-voltage (59), low-voltage (27) and zero-sequence overvoltage (59N), alarm or trip

    • Long start-up time (48), locked rotor (51LR) and reversed phase sequence (47)

    • Non-electrical quantity input

  • product-5712-3213

    Measurement

    • Currents: three phases and I0
    • Voltages: three phases and U0

     

    Interfaces

    • RS-485, with Ethernet as an option
    • Modbus, IEC 60870-5-101, IEC 60870-5-103
    • 12 digital inputs that you define, 6 dry-contact digital outputs

    • A built-in operation box

  • product-1265-949

    Self-diagnosis and records

    • Bus insulation monitoring
    • PT circuit and CT circuit failure detection

    • Operation circuit self-test

    • Fault recording

 

 

Specification Sheet

 

Item

Value

Suitable system

Small-current grounding, 10kV and below, motor protection

Voltage / frequency

100V / 50Hz

Current rating

5A (1A customized)

Power supply

AC/DC 85V–265V or DC 48V

Analog channels

I-three-phase + I0; U-three-phase + U0

Binary channels

12 inputs (user-definable), 6 dry-contact outputs

Communication

RS-485, optional Ethernet

Protocols

Modbus, IEC 60870-5-101, IEC 60870-5-103

Temperature

-30℃ to +55℃

Humidity

not above 95%, no condensation

Pressure

80–110kPa

Reference test atmosphere

15℃–35℃, 45%–75% RH, 86–106kPa

Site requirement

No acid, alkali, corrosive or explosive substances; protected from lightning, rain and snow

Mounting

Flush panel

Size

149mm × 188mm × 108mm

Cutout

139mm × 159mm, ±0.5mm

Tested at

KETOP Laboratory (national relay protection and automation equipment inspection center); IEC-TC95

 

Where It Works

 

product-1264-711

Heavy starters in plant distribution, including conveyor drives, mixers and kiln fans

Pumps, fans, compressors, crushers and ball mills that start often or against high torque benefit from overload, locked-rotor and long-start logic.

product-1672-940

Mines, smelters, chemical works, cement and paper mills

Motor-driven machinery dominates the load, duty cycles are harsh, and the fault record supports root cause analysis.

product-1246-701

Water treatment and lift stations

The relay reports through RS-485 or optional Ethernet to the station SCADA, so unattended sites stay visible from a distant control room.

 

 

Four Steps Inside the Relay

 

Sampling

Three-phase and zero-sequence currents and voltages arrive from the CT and PT circuits, along with the status of the digital inputs.

Evaluation

The processor runs every enabled function in real time, from overload and unbalance to start time, rotor and phase order.

Decision

Once a value crosses its setting and delay, the relay chooses alarm or trip. In parallel it audits the PT, CT and operation circuits, so a wiring defect cannot hide.

Action

A trip goes out through the dry contacts and operation box, the event is stored, and it is published over Modbus, IEC 60870-5-101 or 103.

 

 

Customization You Can Verify

 

product-1267-1027

  • Digital inputs: all 12 are yours to define to match your interlocking and control scheme.
  • Rated current: 5A standard, 1A to suit your CT ratio.

  • Appearance: custom housings are accepted for large orders, since enclosure molds are a significant development cost.

  • OEM/ODM, project integration, technical support and after-sales service.

 

Proof: 144+ customized protection projects at 110kV, 66kV, 35kV and 10kV, in Xinjiang, Gansu, Inner Mongolia, Shandong, Shanxi, Shaanxi, Jiangxi, Guizhou, Yunnan, Hubei and Sichuan, plus distributed PV projects reaching 10.96606 MW in a single installation.

 

Production and Inspection Route

 

  • Automatic SMT placement and AOI; manual component insertion; wave soldering, visual check, touch-up and second AOI.
  • Programming of the CPU board and assembly.
  • First tuning, then 72-hour aging under 24V, 48V or 220V power.
  • Component life check, high-voltage withstand and short-circuit tests.
  • Outgoing inspection: manual full-unit recalibration, then review of front panel, rear cover, screws, lettering, time synchronization within 2s and lens.
product-900-643

 

 

Commercial Terms

 

The NR-620 series has an MOQ of 20 units and carries a 2-year warranty from the date of arrival. Digital I/O and rated current customization must be stated before the order is placed.

 

Recognition and Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711
  • Every product is type-tested at KETOP Laboratory and has passed IEC-TC95 testing.
  • Drafting participant of the national standard for general technical requirements of standardized relay protection devices for 35kV and below (2019 and 2021), and of the energy industry standards NB/T 11054-2023, NB/T 11483-2024 (relay protection for urban rail transit AC power supply systems) and NB/T 11480-2024 (environmental control of outdoor control cabinets in smart substations).
  • State Grid qualified supplier since 2018; National High-tech Enterprise (2013); national "Little Giant" enterprise (2023).
  • Member of the relay protection and automation branch of the China Electrical Equipment Industry Association since 2006, with 70+ patents and software copyrights.

 

 

Selected References

 

 

product-1200-675
  • Flagship: Haixinsha Square opening ceremony power protection at the 16th Asian Games (2010); Three Gorges Yunyang reservoir area.
  • 10kV and 36kV sites: Anda wastewater treatment plant distribution room; Xining Wusi Street underpass distribution; Xiaojiawan coal mine (Panzhihua, 10kV/6kV); Xigou coal mine substation in Fukang; Chayeshu coal mine in Panzhihua; Menyuan Guala No.1 coal mine distribution room in Qinghai; Zhonglian cement plant in Wulatequanqi, Inner Mongolia; Tian'an Chemical 36kV substation.
  • 35kV pumping and chemical: Huachao Chemical (Shandong), Qingjiangkou pump station and the Longshan relay pump station user substation in Jinan.

 

 

Common Questions

 

Q1: Is it a good fit for a motor above 10kV?

No. The NR-624 is limited to small-current grounding systems of 10kV and below. Contact us for higher voltage and we will propose a suitable model.

Q2: How does it differ from a plain thermal overload relay?

It adds measurement, directional and sequence logic, communication, and recording to the overload function.

Q3: What does the overload function do?

It raises an alarm or trips the breaker when motor current stays too high for too long.

Q4: Which communication options exist?

RS-485 as standard, Ethernet as an option; Modbus, IEC 60870-5-101 and IEC 60870-5-103.

Q5: Can inputs and current rating be changed?

Yes: define the 12 inputs yourself and pick 5A or 1A.

Q6: Do you handle OEM/ODM and volume appearance changes?

Yes; large orders can have a custom housing because of the mold investment.

Q7: Minimum quantity and warranty?

20 units; two years counted from arrival.

Q8: Do you supply drawings and commissioning help?

Yes, drawings, wiring diagrams and commissioning support from our engineers.

 

Get a Quote

 

product-1269-952

Reply with project name and place, voltage and frequency, motor application (feeder, pump station, mining, chemical, cement or other), required protection, communication needs (RS-485 or Ethernet; Modbus, 101 or 103), quantity and any customization (inputs, 5A/1A, appearance, OEM/ODM). Attaching the motor nameplate data, CT ratio and a single-line diagram lets our engineers confirm wiring and ordering details quickly, and a reply follows within 24 hours.

 

Request a Quote

 

Hot Tags: motor overload protection relay nr-624, China motor overload protection relay nr-624 manufacturers, suppliers, factory