NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of incomer automatic bus transfer control device nr-500z2 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview

Losing one of two incoming sources should not mean losing the bus. The NR-500Z2 is the device that makes sure it does not. It sits in the incoming-line cabinet, protects the line, and moves the load to the other source when the working supply drops out.
It is the incomer model of the NR-500Z family. The family covers systems up to 110kV, either ungrounded or grounded through an arc-suppression coil. Within a substation automation scheme it acts as the subsystem that watches bus voltage and brings two bus sections together automatically. The sister model, NR-500Z1, handles the sectionalizing switch instead.
The NR-500Z2 is built for schemes that need more than a bare changeover relay. It takes an opposite-side current and an opposite-side voltage on top of the usual three-phase inputs. It offers 16 digital inputs and 14 digital outputs, and carries an integrated operation box. This leaves room to wire breaker positions, interlocks and external signals without adding auxiliary relays.
Because we manufacture it ourselves, the rated voltage, auxiliary supply and I/O count are set to your drawings during production, not adjusted around a fixed catalogue unit.

Key Features & Protection Functions
-

Line and incomer protection
- Overcurrent protection in three stages
- Overload protection
- Zero-sequence overcurrent protection, definite-time and inverse-time
-

Source transfer logic
- Automatic switching of the incoming power supply
-
Automatic return to the original source after recovery
-
Bus insulation monitoring
Built-in watchdogs
- Detection of PT wire breaks
- Detection of CT wire breaks
-
Continuous check of the trip and close circuit
-

Breaker control and records
- Operation box with trip and close self-holding and anti-pumping (anti-jump) function
- Fault waveform recording
Capacity for complex schemes
-
Protection current, measurement current and opposite-side current inputs
-
Three-phase voltage plus opposite-side voltage
-
16 inputs and 14 outputs
-
One RS-485 port as standard, with an extended communication option
Technical Specifications
|
Item |
Specification |
|
Product |
Incomer Automatic Bus Transfer Control Device NR-500Z2 |
|
Function |
Two-way incoming-line cabinet protection and automatic transfer |
|
System voltage |
Up to 110kV |
|
Neutral grounding |
Ungrounded or arc-suppression coil grounded |
|
Current acquisition |
3-phase protection, 3-phase measurement, 1 opposite-side current |
|
Voltage acquisition |
3-phase voltage, 1 opposite-side voltage |
|
Rated AC voltage |
100V (400V on request) |
|
Rated frequency |
50Hz |
|
Working power supply |
AC/DC 110V, AC/DC 220V or DC 48V |
|
Switch inputs |
16 channels |
|
Switch outputs |
14 channels |
|
Communication |
1 × RS-485 standard; optional 2 × RS-485 and 2 × Ethernet |
|
Operation box |
Included, with anti-pumping |
|
Ambient temperature |
-30°C to +55°C |
|
Humidity |
Up to 95%, non-condensing |
|
Air pressure |
80 kPa to 110 kPa |
|
Reference test conditions |
+15°C to +35°C, 45% to 75% humidity, 86 kPa to 106 kPa |
Site requirements. The air around the device should be free of conductive dust and of acid, alkali or explosive vapors. The site must have lightning, rain and snow protection.
Dimensions
|
Drawing |
Size |
|
Front view |
156 mm wide × 232 mm high |
|
Side view |
198 mm overall, 171 mm for the housing |
|
Rear view |
136 mm × 210 mm |
|
Cut-out |
138 mm × 212 mm, minus 1 mm tolerance |
Applications

-
Substations
The main use. The NR-500Z2 guards the two incoming lines of a 110kV-and-below station. It also reports bus voltage status to the station automation system. -
Hydropower
Power stations rely on a second source for plant and auxiliary supply. The device keeps that changeover automatic and protected.

-
Distributed PV
For PV plants that connect through two sources, I/O and rated values can be matched to each switchgear design. -
Industrial & Mining
Metallurgy, chemical, textile, paper and mining sites cannot tolerate a bus blackout. Automatic transfer with automatic return keeps production supplied.

-
Rail & Transportation
Stations and line-side supply rooms use two-source incomers. NAHO contributed to the energy industry standard NB/T 11483-2024 for urban rail AC power supply protection.
How It Works
Collect The Signals
The device measures line current, line voltage, and the opposite-side current and voltage. It also reads breaker states and external contacts through its 16 inputs.
Apply Protection And Supervision
Overcurrent, overload and zero-sequence logic runs continuously. The PT, CT and operating-circuit self-checks run beside it, as does bus insulation monitoring.
Judge The Situation
The device separates a line fault from a lost source and from a sensing failure. This keeps unnecessary operations to a minimum.
Act And Record
The operation box and the 14 outputs trip the breaker and perform the transfer. After the original source returns, the automatic return function restores it. The fault waveform is saved for analysis.
Why Choose NAHO - Custom Engineering Capability

Customization at NAHO is a manufacturing capability and not a sales line.
- Experience you can count. We have delivered tailored solutions for 144+ projects and have worked on electric power automation for over 30 years.
-
Voltage coverage. Our project record spans 110kV, 66kV, 35kV and 10kV, so a two-source scheme at any of these levels is familiar ground.
-
Fixed at the hardware level. Rated voltage (100V or 400V), working supply (AC/DC 110V, AC/DC 220V, DC 48V) and I/O are configured on the production line. Please give us these requirements and note them on the order before production, because they cannot be changed by the user afterwards.
-
Everything made in-house. SMT placement with AOI, plug-in assembly, wave soldering with AOI, CPU board programming, assembly and testing all take place in our own factory.
-
Tested before shipment. Each unit is aged for 72 hours on 24V, 48V or 220V supply, then checked for component life, withstand voltage and short circuits. A final re-tune and inspection of panel, rear cover, screws, printing, lens and clock sync (within 2 s) follow.
-
OEM/ODM and service. We support OEM and ODM orders, project integration, technical support and after-sales service.
-
Custom appearance. Available for large orders only, since housing molds are expensive to develop.
-
Terms. 2-year warranty from the day goods arrive. MOQ for the NR-5XX family is 10 units.
Certifications & Standards




Certificates and test reports
- ISO 9001 quality management certificate
- CE and CCC certificates
- Type-test reports referencing IEC 60255 and IEC 61850
- KETOP Laboratory type-test reports; NAHO's product series have also passed IEC-TC95 international testing
- State Grid qualified supplier proof (from 2018)
Standards we helped write
- The national standard on general technical requirements for 35kV-and-below standardized protection devices
- NB/T 11054-2023, anti-islanding protection devices
- NB/T 11483-2024, relay protection for urban rail AC power supply
- NB/T 11480-2024, environmental control systems for smart-substation outdoor control cabinets
Company recognition
- National high-tech enterprise and national "Specialized, Refined, Distinctive and Innovative" enterprise (2023)
- 70+ patents and software copyrights
- Member of the relay protection and automation branch of the China Electrical Equipment Industry Association since 2006
- Trademark registered in China
Need a specific document for a tender? Tell us, and we will send the copy that matches.
Project References
NAHO's record at the voltage levels where the NR-500Z2 is applied. These are company projects, not a list of NR-500Z2 installations.
|
Project |
Level |
|
Zhengzhou Dali Foods 10kV expansion and renovation |
110kV |
|
Chongqing Ganshui Town capacity-increase power project |
110kV |
|
Jiuquan Jinta Chunlong 110kV substation, Gansu |
110kV |
|
Shanxi Lanxian Fengda Coking waste-heat power project |
66kV |
|
Liaoning Anshan Datongwan Industrial Zone 66kV substation retrofit |
66kV |
|
Kailu Town 66kV/10kV transition substation, Inner Mongolia |
66kV/10kV |
|
Shandong Jinan Longshan relay pumping station user substation |
36kV |
|
Hami Highway Bureau Yandun toll station power distribution, Xinjiang |
35kV |
|
Datong Xingergou Coal Mine 35kV/6kV substation, Shanxi |
35kV |
|
Ningbo Hengmu 35kV PV project |
35kV |
|
Yongci 35kV 15.6 MW distributed PV project |
35kV |
|
Qinghai Chenguang New Energy substation |
10kV |
Other landmark work includes the 2010 Asian Games power supply protection at Haixinsha Square. In PV, our largest single project reaches 10.96606 MW.
FAQ
Q1: What is an incomer automatic bus transfer control device?
It is a relay for a cabinet that receives power from two sources. It protects the incoming line and, when the working source fails, moves the load to the standby one by itself. The NR-500Z2 adds overload and zero-sequence protection, self-checks and fault recording.
Q2: Where is the NR-500Z2 used?
It serves two-source incoming cabinets in systems up to 110kV. Typical sites are substations, hydropower plants, PV projects, mines and industrial plants, and rail power supply.
Q3: Can this device be used in a system with an arc-suppression coil?
Yes. The NR-500Z family is designed for ungrounded systems and for systems grounded through an arc-suppression coil.
Q4: What protection functions does it provide?
Three-stage overcurrent, overload, and definite-time and inverse-time zero-sequence overcurrent protection. It also provides bus insulation monitoring, PT and CT break detection, operating circuit self-check, and fault recording.
Q5: Can protection thresholds and digital I/O be configured or customized?
Rated voltage and digital I/O can be customized. Tell us the requirements before you order, as we set them in hardware at the factory. Customers cannot reconfigure them later.
Q6: What information is required for a quote or selection?
Please send the system voltage and neutral grounding method, the working supply, the rated voltage, how many inputs and outputs you need, the communication ports, panel cut-out details, and the quantity and destination.
Q7: Do you provide OEM/ODM customization?
Yes. Distributors, switchgear builders and integrators can order under their own brand. Custom appearance is possible on large orders.
Q8: Can you provide technical drawings, wiring diagrams and testing support?
Yes. Our engineers support selection, drawings and testing questions. Send us your project details and tell us what you need.
Q9: What is the minimum order quantity?
10 units for the NR-5XX family, which includes the NR-500Z2.
Q10: How long is the warranty?
Two years, starting when the goods arrive.
Get a Quote

Send us your two-source scheme and we will match the NR-500Z2 to it.
Include your voltage level, working supply, rated voltage, I/O needs and quantity. Our engineers will answer with a configuration and a quotation.
Phone: +86 150 5750 1111
WhatsApp / Telegram: 86 13868721792">+86 138 6872 1792
Email: Dr502963156@gmail.com
Address: No. 15 Zhengtai Road, Xinguang Industrial Zone, Liushi, Yueqing, Zhejiang, China
Hot Tags: incomer automatic bus transfer control device nr-500z2, China incomer automatic bus transfer control device nr-500z2 manufacturers, suppliers, factory