Numerical Bus-Tie Automatic Transfer Protection Relay NR-500Z1

Numerical Bus-Tie Automatic Transfer Protection Relay NR-500Z1

Custom-engineered bus-tie auto-transfer protection relay for 110kV-and-below substations and plant distribution, tailored to your grid code and panel layout.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of numerical bus-tie automatic transfer protection relay nr-500z1 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

NH39-2

 

When a substation runs two sources on two bus sections, losing one source should not black out half the site. The NR-500Z1 is the sectionalizing model in NAHO's NR-500Z family and is made for that moment. It guards the bus-tie breaker and manages the source changeover. You get a Numerical Bus-Tie Automatic Transfer Protection Relay in a single panel-mount case instead of a relay plus a separate transfer controller.

The NR-500Z series works in 110kV-and-below networks that are neutral-ungrounded or grounded through an arc-suppression coil. Inside a substation automation system, it watches bus voltage and parallels the two low-voltage bus sections automatically.

 

The unit comes from NAHO (brand NRUICN), a Zhejiang manufacturer in power automation since 1992. We make the NR-500Z1 ourselves, and rated values and I/O are fixed to your order at the factory. In other words, this Bus-Tie Automatic Transfer Protection and Control Relay is built to your scheme and not pulled from a shelf.

product-1200-900

 

 

Key Features & Protection Functions

  • product-1200-800

    Changeover control

    • Incoming-source switch-in and return to normal supply
    • Bus-tie breaker switch-in and return to normal supply

  • product-1200-900

    Fault protection

    • Overcurrent with three time-graded stages
    • Overload detection

     

    Self-supervision

    • Bus insulation monitoring
    • Voltage transformer (PT) and current transformer (CT) wire-break detection

    • Operating-circuit self-test

  • product-1265-949

    Breaker control and records

    • Built-in operation box with trip and close hold, plus anti-pumping
    • Fault waveform recording

     

    Interfaces

    • 16 binary inputs, 14 binary outputs

    • 1 RS485 port as standard; additional ports on request

 

 

Technical Specifications

 

Parameter

NR-500Z1

Role

Bus-tie (sectionalizing) breaker protection and auto-transfer

Network

≤ 110kV; ungrounded or arc-suppression-coil grounded

Current inputs

3 protection + 3 measurement + 2 opposite-side

Voltage inputs

3 phase + 2 opposite-side

Binary inputs / outputs

16 / 14

Serial communication

1 × RS485 (standard)

Operation box

Trip/close hold, anti-pumping

Power supply

AC/DC 110V, AC/DC 220V or DC 48V

Rated AC voltage

100V (400V by customization)

Frequency

50Hz

Ambient temperature

-30 °C to +55 °C

Humidity

up to 95%, no condensation

Air pressure

80 to 110 kPa

Front face

156 × 232 mm

Rear body

136 × 210 mm

Mounting cutout

138 × 212 mm

 

Keep the installation room clear of acid mist, alkaline or corrosive gas and explosive atmospheres, and provide the usual protection against lightning, rain and snow.

 

Applications

 

product-1264-711
  • Substations
    Utility and customer substations with split busbars at 110kV, 66kV, 35kV and 10kV.

  • Hydropower
    Plant auxiliary and station-service boards that need a second source ready when the first is lost.

product-1672-940
  • Distributed PV
    Collector and grid-interface switchgear of rooftop and ground-mounted solar sites, where NAHO's PV references reach 10.96606 MW per project.

  • Industrial & Mining
    Process plants and mines, including steel, chemical, coal, cement and textile, where one dead bus section stops production.

product-1246-701
  • Rail & Transportation
    Traction and wayside power rooms, expressway substations and terminal distribution stations.

 

 

How It Works

 

Sense

The relay reads phase currents, bus voltages and the opposite-side current and voltage, and picks up breaker status from its 16 binary inputs.

Supervise And Compute

Overcurrent and overload elements run next to PT, CT and operating-circuit checks, so bad input data is flagged and not acted upon.

Judge

The logic tells a genuine fault from a dead source. A transfer is only allowed when the conditions are right, which keeps the bus-tie from closing into a fault.

Command

Output contacts trip the faulted breaker or close the tie. After the source recovers, the Bus-Tie Automatic Transfer Protection and Control Relay can restore the original arrangement, and each event is stored as a waveform record.

 

 

Why Choose NAHO – Custom Engineering Capability

 

product-1267-1027

No two transfer schemes match, and our record shows it. Each point below is something you can verify.

 

  • 144+ customized deliveries. These span substations, mines, solar plants and rail, so an unusual layout is routine for us.

  • Four voltage tiers covered. Our project list runs across 110kV, 66kV, 35kV and 10kV.

  • I/O and ratings locked at the factory. Rated values and binary I/O, including 400V rated voltage, are built into the hardware as you specify. Please state them in the order, because they cannot be changed in the field.

  • 30+ years in the same field. We started in 1992 and have stayed focused on power automation since.

  • Custom enclosures for volume. Housing moulds are costly, so appearance customization is accepted for large quantities.

  • Full service range. OEM/ODM, project integration, technical support and after-sales service.

  • Tested before it ships. Each relay passes SMT and AOI, firmware loading, assembly and a 72-hour powered burn-in. Insulation withstand, short-circuit and component-life checks come next, then manual re-tuning and a visual inspection.

  • Warranty: 2 years from the day of arrival. Orders of the NR-5XX series start at 10 units.

 

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711
  • Management system: ISO 9001
  • Product marks and reports: CCC, CE, IEC 60255 and IEC 61850 type test reports
  • Independent testing: KETOP Laboratory type tests and IEC-TC95 international testing
  • Supplier status: State Grid qualified supplier since 2018
  • Standards drafting: the national standard for 35kV-and-below relay protection devices; NB/T 11054-2023 on anti-islanding protection; NB/T 11483-2024 on urban rail AC power supply relay protection; NB/T 11480-2024 on smart substation outdoor cabinet environment control
  • Company honors: national high-tech enterprise, national "specialized, refined, distinctive and innovative" enterprise (2023), 70+ patents and software copyrights

 

 

Project References

 

NAHO's track record, listed here at voltage levels where split buses are typical:

 

product-1200-675
  • Baotou Furong 35kV substation extension, Inner Mongolia
  • Datong Xing'ergou 35kV/10kV and 35kV/6kV substations, Shanxi
  • Mashan 35kV/10kV distribution room, Guangxi
  • Shanghai Hudong Heavy Machinery 35kV–6.3kV distribution
  • Ningbo 35kV photovoltaic project and the 35kV, 15.6MW distributed PV project at Yongci
  • Asian Games Haixinsha opening ceremony power protection (2010)

 

 

FAQ

 

Q1: What does a Numerical Bus-Tie Automatic Transfer Protection Relay do?

It sits on the breaker joining two bus sections. It protects that breaker, and when one incoming source disappears, it closes the tie so the dead section is fed again.

Q2: Which sites use this type of relay?

Substations up to 110kV, factory distribution rooms, mines, PV plants, hydropower stations and rail power facilities that run sectionalized busbars.

Q3: Is the NR-500Z1 suitable for two incoming lines with one bus-tie?

Yes, that is the standard layout it was built for. It watches both sections and handles switch-in and return to normal supply.

Q4: Which protection functions are included?

Three-stage overcurrent, overload, bus insulation monitoring, PT and CT wire-break detection, operating-circuit self-test and fault recording. Zero-sequence overcurrent is not part of this model.

Q5: Can I set protection thresholds and change the I/O?

Thresholds follow your scheme. Rated values and binary I/O are customized in hardware at the factory and cannot be reconfigured afterward, so note them before you order.

Q6: What details do you need to quote?

Single-line diagram, system voltage, neutral grounding, auxiliary supply, rated voltage (100V or 400V), I/O count, communication needs, cutout size and quantity.

Q7: Do you offer OEM/ODM?

Yes, along with project integration and after-sales service. Custom appearance requires a large order volume.

Q8: What are the mounting dimensions?

The front face is 156 × 232 mm, the rear body 136 × 210 mm, and the panel cutout 138 × 212 mm.

Q9: Can you supply drawings, wiring diagrams and test support?

Yes. Our engineers help with selection, drawings and wiring, and each unit is tested before shipment.

Q10: How does it differ from the NR-500Z2?

The Bus-Tie Automatic Transfer Protection and Control Relay NR-500Z1 has two opposite-side voltage inputs and no zero-sequence protection. The NR-500Z2 is for incomer panels and adds zero-sequence overcurrent.

 