NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of incomer automatic bus transfer device nr-311h/v in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview
The NR-311H/V is a microcomputer-based incomer automatic bus transfer device designed for two-way power supply incoming cabinets in small-current grounding systems rated 10kV and below. It combines incoming-feeder protection with automatic switching and auto-recovery of the incoming power supply in one unit. When one incoming supply is lost, the device supports transfer to the other supply, helping keep the bus energized. This reduces the need for a separate protection relay and a separate transfer controller on the same incomer cabinet.
Two independent three-phase voltage inputs monitor the live or dead condition of each incoming line. A programmable auxiliary current channel (Ix) can take the current of the other incomer, which provides a no-current criterion for the transfer logic. Alongside the transfer function, the device provides directional overcurrent, zero-sequence overcurrent, overload and over/low-voltage protection for the incoming cabinet.
The NR-311H/V belongs to the NR-310H/V series, which also includes the NR-310H/V (incoming and feeder cabinet protection), NR-312H/V (section-switch protection and auto-switching) and NR-313H/V (PT cabinet monitoring and protection group). It is available in horizontal (H) and vertical (V) enclosure formats. As the manufacturer, NAHO builds each unit in our own factory in Yueqing, Zhejiang, and offers standard and customized configurations to fit your switchgear design.

Key Features & Protection Functions
-

Automatic Transfer Function
- Auto-switching and auto-recovery of incoming power supply
- Independent live/dead detection of two incoming lines through two three-phase voltage inputs
- No-current criterion supported through the programmable auxiliary current channel (Ix)
-

Protection Functions
- Three-section overcurrent protection with directional lockout (complex voltage lockout)
- Negative-sequence overcurrent protection
-
High-current blocking trip
-
Inverse time-limit overcurrent protection
-
Overload protection (alarm or trip)
-
Three-section zero-sequence overcurrent protection
-
Zero-sequence inverse time-limit overcurrent protection
-
Overcurrent post-acceleration
-
Zero-sequence overcurrent post-acceleration
-
Over/low-voltage protection (alarm or trip)
Measurement Functions
- Three-phase current (Ia / Ib / Ic) plus programmable auxiliary current channel (Ix)
- 2 × three-phase three-wire voltage measurement channels
-

Communication Functions
- RS-485 communication port
- Modbus / IEC 60870-5-101 / IEC 60870-5-103 protocol support
Monitoring & I/O Functions
- 10-way digital input (user-definable)
- 4-way digital output (dry contacts)
Choosing within the NR-310H/V series: use the NR-311H/V for two-way power supply incoming cabinets. For section (bus-tie) switch protection and auto-switching, choose the NR-312H/V. For PT cabinet monitoring and protection, choose the NR-313H/V.
Technical Specifications
|
Parameter |
Specification |
|
Applicable Scope |
Small-current grounding system, 10kV and below; protection and automatic switching for two-way power supply incoming cabinets |
|
Rated Voltage |
100V |
|
Rated Frequency |
50Hz |
|
Rated Current |
5A, 1A (customized) |
|
Auxiliary Power Supply |
AC/DC 85V–265V; DC 48V; DC 24V |
|
Current Protection/Measurement Channel |
3-phase + Ix (programmable auxiliary current channel) |
|
Voltage Measurement Channel |
2 × (3-phase, 3-wire) |
|
Digital Input |
10-way (customizable) |
|
Digital Output |
4-way dry contacts |
|
Communication Port |
RS-485 |
|
Communication Protocol |
Modbus / 101 / 103 |
|
Operating Temperature |
-30℃ ~ +55℃ |
|
Relative Humidity |
≤95%, non-condensing |
|
Atmospheric Pressure |
80–110kPa |
|
Test Standard Atmospheric Condition |
15℃~35℃, 45%~75% RH, 86~106kPa |
|
Dimensions (NR-311H) |
157mm(W) × 74mm(H) × 110mm(D); cutout 147mm(W) × 70mm(H) |
|
Dimensions (NR-311V) |
74mm(W) × 157mm(H) × 110mm(D); cutout 70mm(W) × 147mm(H) |
|
Environment |
Surrounding air must be free of acid, alkali corrosive or explosive substances; lightning, rain and snow protection required |
|
Compliance |
KETOP Laboratory type test; IEC-TC95 international standard testing |
Applications

Dual-incomer switchgear (10kV and below)
Incoming cabinets fed by two independent supplies, where the bus needs to stay energized when one supply fails. The NR-311H/V provides incomer protection and automatic switching in one device.

Industrial dual-circuit power supply
Plant distribution systems in mining, metallurgical and chemical facilities that are supplied by two circuits and need protection and automatic switching on the incoming side.
Scope note: the NR-311H/V is a 10kV-and-below incomer-level device. It is not positioned for high-voltage substation transmission protection, large-scale hydropower or utility-scale PV inverter stations, or main-line rail transit protection.
How It Works
Signal Acquisition
The device samples three-phase current and the auxiliary current channel (Ix). It also samples two independent three-phase line voltages, one from each incoming PT.
Supply Status Evaluation
The voltage inputs of the two incoming lines are evaluated separately to decide whether each supply is live or lost. The Ix channel provides current information from the other incomer for the no-current criterion.
Protection & Transfer Decision
The protection logic checks for faults on the incomer (overcurrent, zero-sequence overcurrent, overload, over/low-voltage). The auto-switching and auto-recovery logic assesses the supply condition.
Trip, Alarm & Switching Output
Through the 4-way dry-contact outputs, the device issues trip and alarm commands and supports automatic switching and recovery of the incoming supply. Status and data are available over RS-485 (Modbus / 101 / 103).
Built Around Your Project, Not Our Catalog

Standard products, non-standard thinking. Every incomer scheme is different. NAHO manufactures the NR-311H/V in our own factory and adapts it to your project instead of fitting your project to a catalog.
- 30+ years of manufacturing experience. Our history goes back to 1992, when our predecessor, Dachang Electric, started in Yueqing Liushi. We have focused on power automation and microcomputer protection ever since.
-
Customization you can verify. On the NR-311H/V, the digital inputs are user-definable, the rated current can be customized to 5A or 1A to match your CT configuration, and horizontal (H) or vertical (V) enclosure formats are available.
-
Full-process OEM/ODM support. We offer OEM/ODM customization, project integration, technical support and after-sales service.
-
Custom enclosure and panel design. We accept large-volume custom enclosure and panel design. Tooling investment is justified once your order volume supports it.
-
Production quality control. Each unit goes through SMT assembly with AOI inspection, CPU programming, initial adjustment, 72-hour power-on aging, withstand-voltage and short-circuit testing, and a final re-adjustment and appearance inspection before shipment.
- Proven across projects. Our 144+ projects cover 110kV to 10kV in 11+ provinces, including distributed PV projects up to 10.96606 MW.
Certifications & Standards




- Type testing: all products pass type tests at the National Relay Protection and Automation Equipment Quality Inspection and Testing Center (KETOP Laboratory).
- International standard testing: IEC-TC95 international standard testing.
- Certificates available: ISO 9001, CCC, CE, IEC 60255 / IEC 61850 type test reports, and KETOP type test reports.
- State Grid qualified supplier: since 2018.
- Standards drafting:
○ General technical requirements for standardized relay protection devices of 35kV and below (national standard), with participation in 2019 and 2021
○ NB/T 11054-2023, Technical Specification for Anti-Islanding Protection Devices
○ NB/T 11483-2024, Technical Specification for Relay Protection of AC Power Supply Systems in Urban Rail Transit
○ NB/T 11480-2024, Technical Specification for Environmental Control Systems of Outdoor Control Cabinets in Smart Substations
- Intellectual property: 70+ patents and software copyrights.
- Corporate qualifications: National High-Tech Enterprise; National-level "Specialized, Refined, Distinctive and Innovative" enterprise (2023).
Case Studies / Project References
The projects below are NAHO NR-series platform references and are not specific to the NR-311H/V.

Featured Projects:
- Haixinsha Square, 16th Asian Games Opening Ceremony (2010): power supply protection and distribution project
- Yunyang Three Gorges Reservoir Project
Project Quick Reference
|
Project |
Voltage Level |
Industry |
|
Zhengzhou Dali Foods 10kV Renovation & Expansion |
110kV |
Food manufacturing |
|
Jiangxi Yuntai Copper 35kV Distribution Project |
35kV |
Metallurgy |
|
Anhui Shengxin Aluminum 35kV Distribution Project |
35kV |
Metallurgy |
|
Shandong Huachao Chemical 35kV Substation |
35kV |
Chemical |
|
Datong Xing'er Gou Coal Mine 35kV/6kV Substation |
35kV/6kV |
Mining |
|
Mulei Yuanda Gold Mine 35kV Substation |
35kV |
Mining |
|
Guangxi Mashan Jixin Industrial 35kV/10kV Distribution Room |
35kV/10kV |
Industrial |
|
Baotou Yaxin Longshun Special Steel |
10kV |
Steel |
|
Panzhihua Xiaojiawan Coal Mine 10kV/6kV Distribution Project |
10kV/6kV |
Mining |
|
Guizhou Xifeng Shidong Switching Station |
10kV |
Power distribution |
|
Inner Mongolia Wind Power Farm |
- |
Wind power |
FAQ
Q1: What is an incomer automatic bus transfer device?
It is a device installed on an incoming cabinet that monitors two incoming power supplies. When the working supply is lost, it supports automatic switching to the other supply and recovery afterwards, so the bus stays powered. The NR-311H/V also provides protection for the incomer.
Q2: Where is the NR-311H/V used?
It is used on two-way power supply incoming cabinets in 10kV and below small-current grounding systems. Typical sites include dual-incomer switchgear and industrial plants in mining, metallurgy and chemicals that are fed by two circuits.
Q3: What is the difference between the NR-311H/V and NR-312H/V?
The NR-311H/V is for incomer cabinets fed by two supplies. The NR-312H/V is for section-switch protection and auto-switching between bus sections. Both belong to the NR-310H/V series.
Q4: What protection functions does the NR-311H/V provide?
It provides three-section overcurrent protection with directional lockout (complex voltage lockout), negative-sequence overcurrent, high-current blocking trip, inverse time-limit overcurrent, overload protection (alarm or trip), three-section zero-sequence overcurrent, zero-sequence inverse time-limit overcurrent, overcurrent and zero-sequence overcurrent post-acceleration, and over/low-voltage protection (alarm or trip).
Q5: How does the device monitor the two incoming supplies?
It has two independent three-phase, three-wire voltage inputs. One connects to each incoming line's PT line voltage. The programmable auxiliary current channel (Ix) can take the other incomer's current, providing a no-current criterion for the transfer logic.
Q6: Can the digital I/O or rated current be customized?
Yes. The 10 digital input channels can be user-defined, and the rated current can be customized to 5A or 1A depending on your CT configuration. Horizontal (H) and vertical (V) enclosure formats are available.
Q7: Do you provide OEM/ODM customization?
Yes. NAHO provides OEM/ODM customization, project integration, technical support and after-sales service. Custom enclosure and panel design is available for large-volume orders.
Q8: Can you provide technical drawings, wiring diagrams and testing support?
Yes. Send us your project details and our engineers will provide the technical documents and support for your selection and commissioning. Products are covered by a 2-year warranty from the date of arrival.
Q9: What information do you need to quote?
Please provide your project name and location, system voltage and frequency, incomer configuration (including PT and CT arrangement), required functions, communication protocol, quantity and any customization requirements.
Q10: What communication protocols does the NR-311H/V support?
It has an RS-485 port and supports Modbus, IEC 60870-5-101 and IEC 60870-5-103.
Get a Quote

Please send us the following so we can quote within 24 hours:
- Project name & location
- System voltage & frequency
- Application type (dual-incomer switchgear / industrial dual-circuit supply / other)
- Incomer configuration (two incoming lines, PT and CT arrangement)
- Required protection functions
- Communication protocol needs
- Quantity
- Customization requirements (digital I/O, rated current, enclosure format H/V, OEM/ODM)
Hot Tags: incomer automatic bus transfer device nr-311h/v, China incomer automatic bus transfer device nr-311h/v manufacturers, suppliers, factory