NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of bus-tie automatic transfer relay nr662 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview

The Bus-Tie Automatic Transfer Relay NR-662□ is a numerical protection and control relay for the bus-section (bus-tie) breaker in a double-source substation. It belongs to the NR-660 series, designed for small-current grounding systems at 66kV and below.
The relay does two jobs in one unit. It protects the bus-tie breaker with directional overcurrent, zero-sequence and voltage protection. It also runs bus-tie auto-transfer and backup-source auto-transfer with auto-recovery. This keeps a healthy section energized when one incoming source is lost, without separate transfer logic in the panel.
NR-662 measures two three-phase, three-wire voltage inputs, one for each bus section. It carries a 5-inch color screen, an integrated operation box and built-in fault recording. It is compact enough to mount directly on the switchgear door.
NAHO builds the unit in our own factory in Yueqing, Zhejiang. The hardware is configured to your order, including rated current, digital inputs and relay outputs.

Key Features & Protection Functions
-

On the bus-section breaker
- Directional overcurrent in three stages, released by voltage condition
- Time-inverse overcurrent curve
-
Overload element with alarm or trip output
-
Post-acceleration after manual or auto closing
Earth-fault elements
- Three-stage zero-sequence overcurrent
- Inverse-time zero-sequence overcurrent
-

Voltage elements
- Overvoltage and undervoltage, each programmable to alarm or trip
-
Busbar insulation monitoring
Source changeover
- Standby-supply switch-in with auto-recovery
-
Bus-section breaker switch-in
-

Device health
- Continuous PT-break, CT-break and operating-circuit supervision
Operator and data
-
5-inch color screen with an integrated operation box
-
Fault waveform recorder
-
Programmable digital inputs
-
RS-485 and Ethernet, speaking Modbus, 101 and 103
Technical Specifications
|
Item |
Specification |
|
Model |
NR-662 |
|
Function |
Bus-tie (sectionalizing) switch protection and automatic transfer |
|
Applicable system |
Small-current grounding systems, 66kV and below |
|
Current measurement channels |
2-phase + 2Ix |
|
Voltage measurement channels |
2 × (3-phase, 3-wire) |
|
Digital inputs |
12 channels, user-definable |
|
Digital outputs |
6–13 dry contacts, customizable |
|
Communication ports |
RS-485 / Ethernet |
|
Protocols |
Modbus / 101 / 103 |
|
Auxiliary power supply |
AC/DC 85–265V, DC 48V |
|
Rated voltage |
100V |
|
Rated frequency |
50Hz |
|
Rated current |
5A or 1A (customizable) |
|
Display |
5-inch color screen |
|
Operating temperature |
-30 to +55 °C |
|
Relative humidity |
≤ 95%, non-condensing |
|
Atmospheric pressure |
80–110 kPa |
|
Front panel size |
149 mm × 188 mm |
|
Depth |
108 mm overall (90 mm body) |
|
Rear size |
138 mm × 158 mm |
|
Panel cut-out |
139 ± 0.5 mm × 159 ± 0.5 mm |
Installation environment: the surrounding air must be free of acid, alkali, corrosive or explosive substances. The device must be protected from lightning, rain and snow.
Applications

-
Substations
Bus-section control for double-source and sectionalized busbar arrangements at 66kV, 35kV and 10kV levels. -
Hydropower
Protection and transfer control for station-service and outgoing distribution sections.

-
Distributed PV
Sectionalizing control in PV station switchgear, backed by commercial and industrial PV projects of up to 10.96606 MW. -
Industrial & Mining
Bus-tie protection for plant substations in metallurgy, chemicals, coal mines, cement, textiles and paper.

-
Rail & Transportation
Distribution rooms and substations for rail, highway and transport infrastructure.
How It Works
Measure
Two-phase current plus 2Ix and two sets of three-phase voltage are read, one voltage set per bus section. Twelve digital inputs bring in breaker states and outside signals.
Evaluate
Current, zero-sequence, overload and voltage elements are evaluated side by side. Supervision of the PT, CT and operating circuit runs in parallel, so a faulty input is flagged rather than trusted.
Decide
The relay distinguishes a fault on the tie circuit from the loss of an incoming source. It then selects a trip, an alarm or a transfer, and logs the event with a waveform.
Act
Dry-contact outputs open the breaker or close the section breaker, so the healthy source supplies both bus sections. The load returns to the normal arrangement under auto-recovery.
Why Choose NAHO - Custom Engineering Capability

- Proof of range. More than 144 sites have received customized solutions from us. They sit at 110kV, 66kV, 35kV and 10kV, in substations, mines, PV plants, hydropower and transport.
-
Hardware built to your drawing. Rated current can be 5A or 1A. Dry-contact outputs can be set anywhere from 6 to 13. Both are fixed during manufacturing, so we ask for them before the order is placed. The end user cannot change them later.
-
Housing changes for volume orders. New tooling is expensive, so custom appearance is offered to large-quantity buyers.
-
Support for resellers and builders. OEM/ODM, project integration, technical support and after-sales service are all available.
-
Quality steps you can audit. Boards pass SMT placement with AOI, then wave soldering with visual check and AOI. Each unit is programmed, assembled and burned in for 72 hours. Component-life, withstand-voltage and short-circuit checks follow, then manual re-tuning and an appearance inspection. Stock entry happens twice before shipment.
-
Experience. The company's roots go back to 1992. We hold 70+ patents and software copyrights, and we have been a State Grid qualified supplier since 2018.
-
After the sale. Two years of warranty start on the arrival date.
Certifications & Standards




Testing. All series have passed type tests at the KETOP laboratory and IEC-TC95 international standard testing.
Documents on file: ISO 9001, CCC, CE, IEC 60255 / IEC 61850 related type test reports, KETOP laboratory reports and the State Grid supplier certificate.
Standards NAHO helped write:
- The national standard covering general requirements for standardized relay protection at 35kV and below
- NB/T 11054-2023 for anti-islanding protection devices (issued February 2023, in force August 2023)
- NB/T 11483-2024 for relay protection in urban rail AC power supply systems
- NB/T 11480-2024 for environmental control systems of smart substation outdoor control cabinets
Standing. National high-tech enterprise, national "specialized, refined, differential and innovative" enterprise (2023), and National Torch Program industrialization project unit.
Project References
These are company-level references at the voltage levels where a sectionalized bus is common:

- Kailu 66kV/10kV transition substation, Inner Mongolia
- Yanji central heating source plant, 66kV–6kV distribution
- Yingkou Deyuan Carbon plant, Liaoning (66kV)
- Lan County Fengda Coking waste-heat power project, Shanxi (66kV)
- Shandong Jinan Longshan relay pump station (36kV and 35kV user substations)
- Yongtaiwen high-speed railway and the Three Gorges Yunyang reservoir area projects
FAQ
Q1: What is a Bus-Tie Automatic Transfer Relay?
It is a protection relay installed on the breaker that joins two bus sections. It guards that link against faults and switches it in when an incoming source is lost. NR-662 does both in one box.
Q2: Where is NR-662 used?
On sectionalized busbars of small-current grounding systems up to 66kV, in utility substations, factories, mines and PV plants.
Q3: Can it serve a double-source substation with two incoming lines?
Yes. It takes one voltage set per bus section and carries standby-source switching with auto-recovery. Send your single-line diagram and we will confirm the I/O.
Q4: What protection functions does it provide?
Directional voltage-controlled overcurrent, inverse-time overcurrent, overload, zero-sequence overcurrent (three-stage and inverse-time), post-acceleration, over/undervoltage and busbar insulation monitoring. It also provides PT/CT supervision and fault recording.
Q5: Can protection thresholds or digital I/O be configured or customized?
The digital inputs can be defined to suit your scheme. Rated current and output hardware are customized in our factory, so list your needs when ordering. After delivery, the end user cannot reconfigure them.
Q6: What information is required for a quote or selection?
Please send the single-line diagram, voltage level, auxiliary supply, rated current, I/O quantities, communication protocol and order quantity. Add your destination country as well.
Q7: Do you provide OEM/ODM customization?
Yes. We handle OEM/ODM, project integration and after-sales support. Custom housings are limited to large orders.
Q8: What are the installation dimensions?
The front measures 149 × 188 mm and the cut-out is 139 ± 0.5 × 159 ± 0.5 mm. The device is 108 mm deep including the front.
Q9: Can you provide technical drawings, wiring diagrams and testing support?
Yes. Our technical team supports selection, drawings and commissioning. Warranty is two years from arrival.
Get a Quote

Planning a sectionalized busbar? Request a quote for Bus-Tie Automatic Transfer Relay NR-662.
Share your single-line diagram, voltage level and I/O list. Our engineers will return a configured proposal.