Incomer Automatic Bus Transfer Protection Device NR-661

Incomer Automatic Bus Transfer Protection Device NR-661

Custom-engineered Incomer Automatic Bus Transfer Protection Device for 66kV and below two-source incomer cabinets, tailored to your grid code and panel layout.
Made by NAHO (NRUICN), a protection relay manufacturer with 30+ years in power automation.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of incomer automatic bus transfer protection device nr-661 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

NH17-2

 

The NR-661 is an Incomer Automatic Bus Transfer Protection Device for two-source incomer cabinets. It belongs to the NR-660 series, which is designed for 66kV and below small-current grounding systems, and it is the series model for incomer cabinets fed from two power sources.

It combines two jobs in one unit. The first is protecting the incomer: directional overcurrent, zero-sequence, negative-sequence, overload and voltage protection. The second is automatic source transfer. When the working source is lost, the device can switch the load to the standby source, and the standby-source self-recovery function is built in.

 

The NR-661 fits the incomer panel directly. It has a 5-inch color screen, a built-in operation box, 12 digital inputs and 6 to 13 dry-contact outputs. It communicates over RS-485 or Ethernet with Modbus, IEC 60870-5-101 and IEC 60870-5-103. Because it mounts on the switchgear itself, it suits distributed installation without a separate relay room.

Every NR-661 is built in our own factory in Yueqing, Zhejiang. Rated values and digital I/O are customized at the factory to your scheme, so you do not have to redesign your panel around the relay.

product-1200-900

 

 

Key Features & Protection Functions

  • product-1265-949

    Incomer Protection

    • Directional three-stage overcurrent protection with composite voltage blocking
    • Inverse-time overcurrent protection
    • Overload protection, set to alarm or trip
    • Negative-sequence overcurrent protection
    • Post-acceleration protection

     

    Earth-Fault Protection

    • Three-stage zero-sequence overcurrent protection
    • Inverse-time zero-sequence overcurrent protection
  • product-5712-4284

    Voltage Protection

    • Overvoltage protection, set to alarm or trip
    • Undervoltage protection, set to alarm or trip

     

    Automatic Transfer

    • Standby power automatic transfer with self-recovery
    • Two three-phase, three-wire voltage inputs, one for each source
  • product-1265-949

    Self-Supervision & Monitoring

    • PT disconnection self-check
    • CT disconnection self-check
    • Operation circuit self-check
    • Busbar insulation monitoring

     

    Recording, Interface & Hardware

    • Fault recording

    • User-definable digital input functions

    • 5-inch color LCD with integrated operation box

    • Integrated temperature and humidity sensor (series feature)

 

 

Technical Specifications

 

Item

Specification

Model

NR-661

Application

Two-source incomer cabinet protection and automatic transfer

System voltage

66kV and below, small-current grounding system

Current inputs

3-phase + Ix

Voltage inputs

2 × (3-phase, 3-wire)

Rated voltage

100V

Rated current

5A (1A customizable)

Rated frequency

50Hz

Auxiliary power supply

AC/DC 85–265V, DC 48V

Digital inputs

12 (input functions user-definable)

Digital outputs

6–13 dry contacts

Communication ports

RS-485 / Ethernet

Protocols

Modbus / IEC 60870-5-101 / IEC 60870-5-103

Display

5-inch color screen

Operating temperature

−30°C to +55°C

Relative humidity

≤95%, no condensation

Atmospheric pressure

80–110 kPa

Front panel size

149 mm × 188 mm

Depth

108 mm overall (90 mm body)

Rear size

138 mm × 158 mm

Panel cutout

139 ± 0.5 mm × 159 ± 0.5 mm

 

The installation site should be free of acidic, alkaline-corrosive or explosive gases in the surrounding air. Rated values and digital I/O are hardware-customized at the factory, so please state them before ordering.

 

Applications

 

product-1264-711
  • Substations
    Protection and source transfer for the incomer cabinets of 66kV and below substations that are fed by two power sources.

  • Hydropower
    Incomer protection for power station auxiliary and plant power systems, where a standby source matters. NAHO has supplied protection for reservoir-area projects such as the Three Gorges Yunyang project.

product-1672-940
  • Distributed PV
    Incomer cabinet protection in the 35kV and 10kV switchgear of commercial and industrial PV projects. Our PV references reach up to 10.96606 MW for a single project.

  • Industrial & Mining
    Two-source supply for plants, mines and process industries, including metallurgy, chemical, textile and paper. Our references include coal mines, gold mines, cement plants and foundries.

product-1246-701
  • Rail & Transportation
    Incomer protection for traction-related power distribution, stations and highway supply rooms. NAHO has taken part in projects such as the Yongtaiwen high-speed railway.

 

 

How It Works

 

Here is how the Incomer Automatic Bus Transfer Protection Device runs, from the first measurement to the final command.

Signal Acquisition

The device samples three-phase current plus Ix, and two sets of three-phase voltage from the two sources. It also reads up to 12 digital inputs, such as breaker positions.

Protection Logic

Overcurrent, zero-sequence, negative-sequence, overload and voltage elements run in parallel. The PT and CT disconnection self-checks run alongside them, so a failed sensing circuit is flagged and not mistaken for a real fault.

Fault Judgment

The device checks each reading against your settings, including direction and composite voltage blocking. It then decides whether to alarm, trip or start a source transfer.

Trip & Transfer Command

Dry-contact outputs trip the incomer breaker. If the transfer conditions are met, the standby source is switched in. Fault records are stored, and the standby-source self-recovery function handles the return of the original source.

 

 

Why Choose NAHO - Custom Engineering Capability

 

product-1267-1027

 

We customize because we build the product ourselves.
Our SMT lines, plug-in lines, wave soldering, programming and assembly are all in-house. A change to a relay configuration is made on our line.

 

  • Proven across scenarios. We have supplied solutions for 144+ projects, from substations and power stations to mines and PV plants. Our approach is that no two custom schemes are the same, and the NR-661□ is built to adapt to that.
  • Voltage range you can verify. Our references run from 110kV through 66kV, 35kV and 10kV, across Xinjiang, Gansu, Inner Mongolia, Shandong, Shanxi, Sichuan and other provinces.

  • Rated values and I/O built to your order. Rated current is supplied as 5A or 1A, outputs range from 6 to 13 dry contacts, and digital input functions are user-definable. Rated values and digital I/O are fitted at the factory, so tell us your requirements before you order.

  • Thirty-plus years of focus. NAHO has concentrated on power automation since 1992, and was founded as Dachang Electric in Yueqing.

  • Certified and tested before it leaves. Our quality system is ISO 9001 certified, and our products carry CE and CCC certification. Each unit goes through a 72-hour burn-in on 24V, 48V or 220V supply, a withstand-voltage test, a short-circuit check and a final inspection of the front panel, rear cover, screws, printing and time synchronization.

  • Appearance customization for volume orders. Because new housing molds are costly to develop, we accept custom appearance on larger order quantities.

  • OEM/ODM, integration and support. We offer OEM and ODM manufacturing for distributors, panel builders and system integrators, plus project integration, technical support and after-sales service, with a 2-year warranty counted from arrival.

 

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711

Quality & Product Certification

  • ISO 9001 quality management system certification
  • CE certification
  • CCC certification
  • Type test reports related to IEC 60255 and IEC 61850
  • KETOP Laboratory type test reports. KETOP is the National Relay Protection and Automation Equipment Quality Inspection and Testing Center, and all NAHO relay series are also tested to IEC-TC95 international standards.
  • State Grid qualified supplier certificate (since 2018)

Standards Participation

  • Participated in drafting the national standard for general technical requirements of standardized relay protection devices for 35kV and below.
  • Participated in drafting energy industry standards NB/T 11054-2023 (anti-islanding protection devices), NB/T 11483-2024 (relay protection for urban rail AC power supply) and NB/T 11480-2024 (outdoor control cabinet environmental control systems for smart substations).

 

Qualifications & Recognition

  • National High-tech Enterprise
  • National Specialized and Innovative "Little Giant" Enterprise (2023)
  • 70+ patents and software copyrights
  • Member of the relay protection and automation equipment branch of the China Electrical Equipment Industry Association since 2006
  • Registered trademark in China

 

Certificates are available on request. Tell us what your project or tender requires and we will send the matching documents

 

 

Project References

 

 

Project

Voltage Level

Gansu Zhangye Shandan Tieqi Cement 110kV substation

110kV

Jilin Yanji Central Heating Plant 66kV–6kV power distribution

66kV–6kV

Jilin Haigou Gold Mine 66kV distribution room retrofit

66kV

Inner Mongolia Baotou Furong 35kV substation expansion

35kV

Shandong Jinan Taian 35kV step-down station

35kV

Tibet Dangdui 35kV substation

35kV

Guizhou Zunyi Tongzi highway 35kV construction substation

35kV

Qinghai Golmud Salt Lake 35kV substation

35kV

Shanxi Luan Environmental Energy, Zhangcun Coal Mine, Zone 1

10kV

Inner Mongolia Urad Front Banner Zhonglian Cement Plant

10kV

Zhejiang Liyi Precision 10.96606 MW distributed PV project

PV

 

 

Signature NAHO projects

 

 

product-1399-872
  • Power supply protection and distribution for the opening ceremony of the 16th Asian Games (2010), Haixinsha Square
  • Three Gorges Yunyang reservoir area project
  • Inner Mongolia wind farm
  • Yongtaiwen high-speed railway

 

 

FAQ

 

Q1: What is an Incomer Automatic Bus Transfer Protection Device?

It is a relay installed in an incomer cabinet that is fed by two power sources. It protects the incomer against faults and automatically switches the load to the standby source when the working source is lost. The NR-661 combines both functions in one unit.

Q2: Where is the NR-661 used?

It is used in two-source incomer cabinets in 66kV and below systems, including substations, power stations, industrial plants, mines, PV projects and rail power supply.

Q3: Can this device be used for my project?

It suits 66kV and below small-current grounding systems with two incoming sources. Send us your single-line diagram, and we will confirm whether the NR-661□ fits or whether another NR-660 series model, such as the NR-660□ for incomer and feeder cabinets, is the better choice.

Q4: What protection functions does it provide?

Directional three-stage overcurrent with composite voltage blocking, inverse-time overcurrent, overload, three-stage and inverse-time zero-sequence overcurrent, negative-sequence overcurrent, post-acceleration, and overvoltage and undervoltage protection. It also provides PT and CT disconnection self-check, busbar insulation monitoring and fault recording.

Q5: Can protection thresholds and digital I/O be configured or customized?

Protection thresholds are set to your scheme, and overload, overvoltage and undervoltage can each be set to alarm or trip. Rated values and digital I/O are customized in hardware at our factory, so you need to state them in your order notes before production. They cannot be reconfigured on site afterwards. Rated current can be 5A or 1A.

Q6: Which certifications does the NR-661 come with?

NAHO holds ISO 9001, CE and CCC certification, plus KETOP Laboratory type test reports and type test reports related to IEC 60255 and IEC 61850. Our products are also tested to IEC-TC95 standards. Tell us which documents your project requires and we will send the matching copies.

Q7: Do you provide OEM/ODM customization?

Yes. We offer OEM and ODM manufacturing, which suits distributors, switchgear builders and system integrators who want their own label. Custom appearance is available for larger order quantities, because the housing mold requires a separate development cost.

Q8: What information is required for a quote or selection?

Please send your system voltage, a single-line diagram of the two sources, CT/PT ratios, the rated current (1A or 5A), the auxiliary supply, the number of digital inputs and outputs you need, the communication protocol, the quantity, and any special transfer requirements.

Q9: Can you provide technical drawings, wiring diagrams and testing support?

Yes. We provide dimension and cutout drawings, wiring support and technical assistance. The unit is 149 × 188 mm at the front and mounts in a 139 × 159 mm panel cutout.

Q10: What is the warranty and the minimum order quantity?

The warranty is 2 years from the date the goods arrive. The minimum order quantity is confirmed with each quotation.

 

Get a Quote

 

product-1269-952

Tell us your two-source scheme. We will match the NR-661 to it.

Send your voltage level, single-line diagram, CT/PT data, rated values and I/O requirements, and quantity. Our engineers will reply with a selection proposal and a quotation.

Request a Quote

 

Hot Tags: incomer automatic bus transfer protection device nr-661, China incomer automatic bus transfer protection device nr-661 manufacturers, suppliers, factory