NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of busbar automatic bus transfer device nr-312h/v in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview
The NR-312H/V is a microcomputer-based Busbar Automatic Bus Transfer Device for small-current grounding systems rated 10kV and below. It sits on the bus-section (sectionalizing) switch and does two jobs. It protects the section switch, and it automatically restores supply to a dead bus section from the healthy one.
In a double-bus or sectionalized-bus substation, losing one incoming source drops every feeder on that section. The NR-312H/V monitors both sections through two independent three-phase voltage inputs. When one section loses supply, it carries out the transfer through the section switch. When normal supply returns, the incoming source can switch back automatically. Overcurrent, zero-sequence and voltage protection work on the same platform, so the section switch does not need a separate protection relay.
The device belongs to the NR-310H/V series. Its sister models cover feeder and incomer duty (NR-310H/V), dual-source incomer transfer (NR-311H/V) and PT cabinet monitoring (NR-313H/V). It comes in a horizontal (H) or vertical (V) enclosure, so it can fit your existing panel cut-out. It is built to be configured around your project, with digital inputs and rated current specified before production.

Key Features & Protection Functions
-

Automatic Transfer Functions
- Section-switch automatic transfer (bus-section reserve power auto-switching)
- Incoming power supply auto-switching and auto-recovery
- Two independent three-phase, three-wire voltage inputs for monitoring both bus sections
-

Overcurrent Protection
- Three-stage overcurrent protection with complex-voltage lockout and direction control
-
Inverse-time overcurrent
-
High-current lockout of tripping
-
Negative-sequence overcurrent protection
-
Overcurrent post-acceleration
-
Overload protection, configurable for alarm or trip
Earth-Fault Protection
- Three-stage zero-sequence overcurrent protection
- Zero-sequence inverse-time overcurrent
-
Zero-sequence overcurrent post-acceleration
-

Voltage Protection
- Overvoltage and undervoltage protection, configurable for alarm or trip
Inputs, Outputs & Communication
- 9 digital inputs, with user-defined input assignment
- 6 dry-contact outputs
-
RS-485 port with Modbus, IEC 60870-5-101 and IEC 60870-5-103 protocols
Technical Specifications
|
Parameter |
Specification |
|
Model |
NR-312H/V (H = horizontal, V = vertical enclosure) |
|
Device type |
Section-switch protection and automatic transfer relay |
|
System voltage / grounding |
10kV and below, small-current grounding system |
|
Current measurement channels |
2 phase + 2Ix (per configuration table) |
|
Voltage measurement channels |
2 × (3-phase, 3-wire) |
|
Digital inputs |
9, user-defined |
|
Digital outputs |
6 dry contacts |
|
Communication port |
RS-485 |
|
Communication protocols |
Modbus / 101 / 103 |
|
Auxiliary power supply |
AC/DC 85V–265V, DC 48V, DC 24V |
|
Rated voltage |
100V |
|
Rated frequency |
50Hz |
|
Rated current |
5A (1A available on request) |
|
Operating temperature |
-30°C to +55°C |
|
Relative humidity |
≤95%, non-condensing |
|
Atmospheric pressure |
80–110kPa |
|
Dimensions, NR-312H |
157mm (W) × 74mm (H) × 110mm (D) |
|
Dimensions, NR-312V |
74mm (W) × 157mm (H) × 110mm (D) |
|
Panel cut-out, H / V |
147 × 70mm / 70 × 147mm |
|
Compliance |
KETOP Laboratory type test; IEC-TC95 international standard testing |
Environment note: the air around the device must be free of acid, alkali corrosives and explosive substances, and the installation needs lightning, rain and snow protection.
Applications

-
Substations
Bus-section switches in 10kV and below substations, where a lost incoming source must be covered by the other section without a long outage. -
Hydropower
10kV and below distribution sections inside power-plant premises that run split-bus arrangements.

-
Distributed PV
On-site 10kV and below distribution rooms of industrial and commercial PV projects that use sectionalized buses. -
Industrial & Mining
Mine, steel, chemical and manufacturing plant substations where one dead section means stopped production.

-
Rail & Transportation
10kV and below distribution sections in transport facilities, such as highway and station power rooms.
Scope note: NR-312H/V is a 10kV-and-below section-level device. It is not positioned for high-voltage transmission protection, utility-scale generation stations or main-line traction protection.
How It Works
Signal Acquisition
The relay samples section-switch current and the two independent three-phase bus voltages, so it sees the condition of both sections.
Protection Logic Processing
The measured values run through the enabled overcurrent, zero-sequence and voltage logic, together with the automatic-transfer logic.
Fault & Loss-of-Supply Judgment
The device decides whether the section switch faces a fault, or whether one section has lost its source and the other is healthy.
Trip / Transfer Command
Through the dry-contact outputs, the relay either trips the section switch or issues the transfer command. Alarm and trip states are reported over RS-485.
Why Choose NAHO

Specific to your sectionalized bus, not a catalogue default.
- Built to your wiring. Digital I/O quantity and rated current (5A or 1A) are set in hardware at our factory. Please state them on the order, since they cannot be reconfigured on site later.
-
Three decades in power automation. NAHO began in 1992 and has worked on protection and automation ever since.
-
Wide scenario record. We have supplied customized solutions for 144+ projects, from 10kV substations to 110kV stations, in more than 11 provinces.
-
One body, two orientations. The H and V formats share the 157 × 74 × 110mm size, so the relay fits panels laid out either way.
-
Factory-controlled quality. From SMT with AOI to the 72-hour aging and withstand-voltage test, every unit passes our own production line.
- Brand and service options. OEM/ODM, project integration, technical support and after-sales service are available. Custom appearance is open to large orders.
-
Terms. MOQ is 20 units for the NR-310 series, and the warranty is 2 years from arrival.
Certifications & Standards




- Compliance and test evidence
NR-312H/V ships with ISO 9001 quality system certification, CCC and CE marks, and IEC 60255 / IEC 61850 type test reports. The NR-series has been type-tested at the KETOP Laboratory, the national relay protection and automation test center, and has passed IEC-TC95 international standard testing. English copies are available for tender files. - Supply qualification
NAHO has been on the State Grid qualified supplier list since 2018. We are a National High-tech Enterprise and a national-level "Specialized, Refined, Distinctive and Innovative" enterprise (2023), holding 70+ patents and software copyrights. We joined the relay protection and automation branch of the China Electrical Equipment Industry Association in 2006.
Standards written with our participation
- General technical requirements for standardized relay protection devices, 35kV and below (national standard)
- NB/T 11054-2023, anti-islanding protection devices
- NB/T 11483-2024, relay protection for urban rail transit AC power supply
- NB/T 11480-2024, environmental control systems for smart-substation outdoor cabinets
Project References
|
Project |
Level / Type |
|
Jiangxi Yuntai Copper distribution project |
35kV |
|
Anhui Shengxin Aluminum distribution project |
35kV |
|
Shandong Liaocheng Weisdel Aluminum |
35kV |
|
Guizhou Zunyi Tobacco logistics center substation |
35kV |
|
Baotou Shengxin Energy data center distribution room, Inner Mongolia |
35kV |
|
Guangxi Mashan Jixin distribution room |
35kV/10kV |
|
Qinghai Xining Sunshine Energy substation |
35kV |
|
Hubei Shennongjia Shennong Hotel distribution station |
10kV |
|
Zhejiang Liyi Precision distributed PV project |
10.96606 MW |
|
2010 Asian Games Haixinsha Square power supply protection |
Landmark project |
These are NAHO NR-series platform references, not a list of NR-312H/V installations. Specific references are available on request.
FAQ
Q1: What is a Busbar Automatic Bus Transfer Device?
It is a relay installed on the bus-section switch. When one section loses its supply, it closes the section switch so the other source feeds the dead section. The NR-312H/V also protects the section switch itself.
Q2: Where is the NR-312H/V used?
It is used on sectionalized buses at 10kV and below in substations, industrial plants, mines and on-site distribution rooms.
Q3: Can this device be used for a single-source system?
It is designed for sectionalized arrangements with two sources, where a section switch exists. For a single-feeder cabinet we recommend the NR-310H/V, and for dual-source incomer cabinets the NR-311H/V.
Q4: What protection functions does it provide?
Three-stage overcurrent with complex-voltage lockout and direction, inverse-time overcurrent, negative-sequence overcurrent, overload, three-stage zero-sequence overcurrent, zero-sequence inverse-time, post-acceleration, and overvoltage and undervoltage protection.
Q5: Can protection thresholds and digital I/O be customized?
Digital input assignment is user-defined. Digital I/O quantity and rated current (5A or 1A) are customized in hardware, so you must specify them before ordering. They cannot be changed on site afterwards.
Q6: What information is required for a quote or selection?
Please send the system voltage and frequency, bus arrangement, CT ratings, power supply, required protection functions, communication protocol, enclosure format (H or V), quantity and any customization requirements.
Q7: Do you provide OEM/ODM customization?
Yes. We provide OEM/ODM, project integration, technical support and after-sales service. Appearance customization needs large order volumes.
Q8: Which communication protocols are supported?
RS-485 with Modbus, IEC 60870-5-101 and IEC 60870-5-103.
Q9: What is the minimum order quantity and warranty?
The MOQ for the NR-310 series is 20 units. The warranty is 2 years from the date of arrival.
Q10: Can you provide technical drawings, wiring diagrams and testing support?
Yes. Dimension and cut-out drawings are available, and we offer technical support and after-sales service for commissioning. Every unit is aged for 72 hours, then tested for withstand voltage, short circuit and timing before shipping.
Get a Quote
Need a Busbar Automatic Bus Transfer Device built around your switchgear?
Send us your section arrangement and I/O requirements, and our engineers will recommend a configuration.

Please include:
- Project name and location
- System voltage and frequency
- Bus arrangement (sectionalized, dual-source)
- Required protection and transfer functions
- Communication protocol
- Enclosure format (H or V), quantity
-
Customization requirements (I/O, rated current, appearance)
Contact:
Phone: +86 150 5750 1111
WhatsApp / Telegram: 86 13868721792">+86 138 6872 1792
Email: Dr502963156@gmail.com
Hot Tags: busbar automatic bus transfer device nr-312h/v, China busbar automatic bus transfer device nr-312h/v manufacturers, suppliers, factory