NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of motor protection relays nr-614 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
NR-614 Motor Protection Relays for 10kV and Below Motor Cabinets

Product Introduction
Motor protection relays decide whether a stalled pump or a jammed crusher ends with a clean trip signal or a burnt stator, and the NR-614 is NAHO's answer for motor cabinets in small-current grounding networks up to 10kV. It is a microcomputer unit that watches the feeder continuously and operates the breaker the moment a measured quantity leaves its safe window.
We are the plant behind the label. NAHO grew out of Dachang Electric, founded in 1992 in the Liushi electrical district of Yueqing, and every NR-614 is still placed, soldered, programmed, aged and inspected on our own lines at No. 15 Zhengtai Road, Xinguang Industrial Zone, Yueqing, Zhejiang. Buying direct means questions about firmware, wiring or special orders reach the engineers who built the device.
Where the NR-614 Fits in the NR-610 Family
The NR-614 is the motor-cabinet member of a six-model family that shares one hardware platform:
- NR-610 – incoming and outgoing feeder cabinets
- NR-611 – dual incoming supply with automatic transfer
- NR-612 – sectionalizing switch protection with automatic transfer
- NR-613 – PT cabinet, monitoring and paralleling of two PT groups
- NR-613A – PT cabinet, monitoring and protection of one PT group
-
NR-614 – motor cabinet
A panel builder who mixes these cabinet types keeps a single wiring routine, one communication setup and one set of spare parts across the whole lineup.

Core Strengths
Starting-duty awareness:
The relay supervises how long a start takes, recognizes a rotor that refuses to turn and checks the incoming phase order before the motor is energized into damage.
01
Broad fault coverage:
Current, earth leakage, unbalance, overload and voltage disturbances are all handled by a single device, each with its own alarm or trip choice.
02
Self-checking hardware:
The relay audits its own PT and CT wiring and the breaker control loop, so a loose terminal is reported instead of silently disabling protection.
03
Evidence after the event:
Fault records let maintenance staff reconstruct what happened without guessing.
04
Plug-in for automation:
An RS-485 port speaks Modbus, IEC 60870-5-101 and IEC 60870-5-103.
05
Key Features & Protection Functions
-

Protection Suite
- Motor start and rotor: excessive start time (ANSI 48), locked rotor (ANSI 51LR), reverse phase sequence of the voltage (ANSI 47).
- Phase faults: three-stage overcurrent with complex-voltage blocking and direction control (ANSI 50/51, 67), an inverse-time curve, and a blocking trip for very high currents.
-
Thermal load: overload, configurable as warning or trip.
-
Ground faults: three-stage zero-sequence overcurrent (ANSI 50N/51N).
-
Unbalance: negative-sequence overcurrent (ANSI 46).
-
Voltage: overvoltage (59), undervoltage (27) and zero-sequence overvoltage (59N), each switchable between warning and trip.
-
Others: non-electrical quantity protection.
-
Supervision: bus insulation monitoring, PT and CT broken-wire detection, operation circuit check, event recording.
-

Technical Data
- Electrical: Rated voltage 100V, rated frequency 50Hz. Rated current 5A, or 1A when the order specifies it. Auxiliary supply: AC/DC 85V to 265V, DC 48V or DC 24V.
-
Signals and interfaces: Analog: three phase currents plus I0, three phase voltages plus U0. Binary: 10 user-defined inputs and 5 dry-contact outputs. Serial: RS-485 with Modbus, IEC 60870-5-101 or IEC 60870-5-103.
-
Environment: Working temperature from -30℃ to +55℃, humidity up to 95% without condensation, air pressure 80 to 110kPa. Reference test conditions: 15℃ to 35℃, 45% to 75% RH, 86 to 106kPa. The site must be free of acidic, corrosive or explosive gas and sheltered from lightning, rain and snow.
-
Mechanical: Flush panel mounting. Case 128mm wide, 188mm high, 108mm deep including the front bezel; the body behind the panel is 90mm deep. Cutout 123mm × 143mm, tolerance ±0.5mm.
-

Typical Applications
- Pump, fan and compressor feeders in the distribution rooms of mines, smelters, chemical works, cement lines and paper mills.
-
Crushers and ball mills whose long, heavy starts make start-time supervision and locked-rotor logic valuable.
-
Pumping stations for water supply and drainage, where a remote operator needs fault data over RS-485.
Operating Principle
Every cycle the NR-614 reads the cabinet's CT and PT signals, compares them with the enabled protection settings, classifies any deviation, and then either raises a warning or opens the breaker through a dry contact. The fault record is stored and can be pulled by the supervisory system over the serial link.
Why Buy from NAHO

You get a manufacturer's flexibility on a catalog product. The NR-614 accepts user-defined digital inputs so the relay matches your cabinet's signals, and a 1A secondary instead of the standard 5A when your CTs require it. Customers who order in volume can also commission a dedicated enclosure and panel layout, because mold tooling only pays off at scale. OEM/ODM supply, project integration, technical support and after-sales service come from the same team.
Experience behind it: more than 30 years in power automation, 144+ delivered projects between 110kV and 10kV across Xinjiang, Gansu, Inner Mongolia, Shandong, Shanxi, Shaanxi, Jiangxi, Guizhou, Yunnan, Hubei, Sichuan and further provinces, in power, mining, steel, chemical, construction and transport.
How Each Relay Is Built and Checked
Boards go through automated SMT placement and AOI, then manual through-hole insertion and wave soldering followed by visual inspection and a second AOI pass. After the first warehouse entry the CPU board is programmed and the unit assembled. Initial adjustment is followed by 72 hours of aging on 24V, 48V or 220V supply, a component life check, a withstand-voltage test and a short-circuit test. Before packing, an operator recalibrates each complete unit and inspects the front panel, back cover, screws, printed text, clock synchronization (within 2 seconds) and display lens.

Order Information




Minimum order: 20 units for the NR-610 series, which includes the NR-614. Warranty: 2 years starting on the day the goods arrive. Customized digital I/O or rated current must be stated and noted on the order before production, because the hardware is customized at the factory and cannot be reconfigured by the customer afterwards.
Credentials

Type tests at the KETOP Laboratory, the national quality inspection and testing center for relay protection and automation equipment, and IEC-TC95 testing. Documents you can request: ISO 9001, CCC, CE, IEC 60255 and IEC 61850 type test reports, and the State Grid qualified supplier certificate held since 2018. NAHO contributed to the national standard on general technical requirements for standardized relay protection devices of 35kV and below (2019, 2021) and to NB/T 11054-2023 on anti-islanding protection devices, in force from August 6, 2023. The company is a national high-tech enterprise and a 2023 national "little giant" specialized and innovative enterprise, has belonged to the relay protection branch of the China Electrical Equipment Industry Association since 2006, and holds over 70 patents and software copyrights.
Reference Projects
Landmark Work
Protection and distribution for the opening ceremony of the 16th Asian Games at Haixinsha Square (2010), and the Three Gorges Yunyang reservoir area project.
Mining And Metals
A gold mine's 66kV distribution room rebuild in Jilin, an iron mine substation in Hebei, a gold mine substation in Xinjiang, a copper-molybdenum phase II 10kV scheme and a special steel works in Inner Mongolia, an aluminum plant in Shanxi, and a Sichuan coal mine.
Process Industry And Materials
A coking plant waste heat generation project in Shanxi (66kV), a Shandong chemical company and a Qinghai salt lake substation (35kV), and an Inner Mongolia cement plant (10kV).
Water
A wastewater treatment plant distribution room in Heilongjiang (10kV).
FAQ
Q1: What do motor protection relays actually do?
They monitor a motor feeder's current and voltage and open the breaker when overload, a locked rotor or a voltage anomaly appears, protecting both the motor and the network behind it.
Q2: Is the NR-614 meant for asynchronous motors?
Yes, that is its main target, in systems up to 10kV.
Q3: Which functions are included?
Start-time, locked-rotor and phase-sequence protection, plus the overcurrent, earth fault, unbalance, overload and voltage functions listed in section 4.
Q4: Can it report to a SCADA system?
Yes, through RS-485 using Modbus or IEC 60870-5-101/103.
Q5: What can be tailored?
The ten digital inputs, the 5A or 1A rated current and, for large orders, the enclosure and panel design.
Q6: What are the minimum order and the warranty?
Twenty units, and two years from arrival.
Q7: Will you send drawings and help with commissioning?
Yes: dimension and cutout drawings, wiring diagrams and commissioning support are available.
Get a Quote

Send our engineers the project name and location, system voltage and frequency, the kind of motor cabinet, the protection functions you need, your communication protocol, the quantity and any customization. They answer within 24 hours.
Hot Tags: motor protection relays nr-614, China motor protection relays nr-614 manufacturers, suppliers, factory