NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of self-powered numerical protection relay nr-321 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview

Some cabinets leave only a low, wide window on the door for protection equipment. The NR-321 is made for that layout. It is the horizontal version of NAHO's CT-supplied relay family, with a 153 × 78 mm front panel and a 148 × 72 mm cut-out.
As a Self-Powered Numerical Protection Relay, it takes its working energy from the current transformer of the protected circuit. Cabinet builders can therefore leave out the DC panel or UPS that a battery-fed relay would need. This matters in unattended box-type substations and small ring cabinets, where adding a station battery is costly or impractical.
The relay fits a circuit-breaker cabinet and a load-break-switch-plus-fuse cabinet. It provides phase and zero-sequence overcurrent protection, external-contact tripping, and a passive trip output that drives the trip coil directly. It has an English LCD interface and RS-485 communication.
NAHO builds the NR-321 in its own factory in Yueqing, Zhejiang. Rated current, trip voltage and communication interface are therefore fixed against your order, not picked from a fixed catalogue.

Key Features & Protection Functions
-

What it protects against
- Overload and short-circuit faults: two-stage definite-time overcurrent and inverse-time overcurrent
- Earth faults: definite-time and inverse-time zero-sequence overcurrent
- Remote or equipment-triggered faults: direct trip from an external contact
- Fuse-coordinated circuits: high-current blocking trip, which handles the protection dead zone in distribution systems
-

Settings and curves
- Several IEC inverse-time curves to choose from
-
Every protection function can be put in or taken out of service through the menu
-

Installation and use
- Landscape front panel, simple compact structure, easy to fit in tight cabinets
-
English LCD with multi-level menus
-
100 historical event records in non-volatile memory, kept through power loss
-
Static and dynamic self-checking of all parts of the device
-
Front RS-232 port for commissioning, and a rear RS-485 port with an open protocol for SCADA
Technical Specifications
Mechanical (NR-321, horizontal mounting)
|
Item |
Value |
|
Front panel |
153 mm × 78 mm |
|
Body length |
147 mm |
|
Depth |
120 mm |
|
Panel cut-out |
148 mm × 72 mm |
Electrical
|
Item |
Value |
|
Auxiliary supply |
DC20V–100V or DC220V |
|
Rated current |
5A (1A on request) |
|
Rated frequency |
50Hz |
|
Trip output |
DC24V or DC220V |
|
CT-supply start-up power |
0.2VA |
Environment
|
Item |
Value |
|
Temperature |
−30°C to +55°C |
|
Humidity |
≤95%, no condensation |
|
Pressure |
80–110kPa |
The installation site must be free of acid, alkali and explosive substances. The unit is rated for lightning, rain and snow protection test conditions. Reference conditions for testing are +15 to +35°C, 45%–75% humidity and 86–106kPa.
Applications

-
Substations
Box-type substations and ring cabinets, where the CT supplies the relay and no battery is fitted. -
Hydropower
Small distribution cabinets in power station auxiliary systems.

-
Distributed PV
Compact distribution cabinets at rooftop PV sites. Our PV references run from about 1.4MW to 10.96606MW. -
Industrial & Mining
Cabinets feeding plant, mine, pumping and heating loads, protecting lines, distribution transformers, motors and capacitors.

-
Rail & Transportation
Compact cabinets for road and rail infrastructure. NAHO took part in drafting NB/T 11483-2024 for urban rail AC power supply protection.
How It Works
Draw Power And Sample Current
The power CT feeds the relay. Measuring winding is normally used, with no accuracy class required, as long as its capacity covers the 0.2VA start-up power.
Run The Protection Logic
Phase and zero-sequence currents are checked against the settings of each enabled function.
Judge The Fault
The relay decides whether a setting and its delay or curve have been met. For very high currents it blocks the trip so the fuse can clear the fault.
Issue The Trip
The passive output drives the trip coil directly. An external contact can also trip. The event is stored and can be read by SCADA.
CT sizing guide
- At 10% of the CT rated current, the secondary output should be 12V or more.
- At 50%, it should be 25V or more.
- At 100%–200%, it should be 25V or more and under 30V.
- The open-circuit voltage must stay under 40V once the current exceeds the CT rated value.
Why Choose NAHO - Custom Engineering Capability

Configured for your cabinet, then built.
- Hardware set at order: rated values and digital I/O are customized in hardware. You state them before ordering, and the unit cannot be reconfigured by the user afterward.
- Supply and trip voltage: DC20V–100V or DC220V supply, with DC24V or DC220V trip output. You choose the pair.
- Rated current: 5A, or 1A as a customization.
- Orientation: vertical NR-320 or horizontal NR-321, to match your door cut-out.
- Appearance: custom exterior on high-volume orders, because housing mould development is expensive.
Facts behind the claim
- 144+ project scenarios in our references, from 110kV to 10kV.
- Power automation focus for over 30 years, since 1992.
- 70+ patents and software copyrights.
- OEM/ODM, project integration, technical support and after-sales service.
What happens to every unit in our factory
- SMT placement with AOI inspection, plug-in assembly, wave soldering and a further AOI check
- First warehouse entry, then CPU program burn-in and assembly
- Initial tuning, then a 72-hour aging test with 24V, 48V or 220V power
- Component life check, withstand-voltage test and short-circuit check
- Final inspection: re-tuning, appearance check of panel, rear cover, screws, printing and lens, and time synchronization within 2 seconds
- Packing, second warehouse entry and shipment
-
Warranty: 2 years from the date the goods arrive.

Certifications & Standards




NAHO products pass type tests at the KETOP laboratory of the National Relay Protection and Automation Equipment Quality Inspection Center and IEC-TC95 international standard testing. The company holds ISO 9001, CCC and CE certification, IEC 60255 / IEC 61850 type test reports and State Grid qualified supplier status (since 2018).
NAHO is a National High-tech Enterprise and a National Specialized, Refined, Distinctive and Innovative enterprise (2023). It has been a member of the relay protection and automation branch of the China Electrical Equipment Industry Association since 2006. We took part in drafting the national standard for 35kV-and-below protection devices, and three NB/T standards: 11054-2023, 11483-2024 and 11480-2024.
Project References

NAHO company-level references, not all with the NR-321:
- Jilin Yanji heating plant, 66kV–6kV power distribution
- Gansu Zhangye Shandan, 110kV substation
- Xinjiang Hami highway toll station, 35kV power distribution
- Inner Mongolia Baotou, data center 35kV distribution room
- Zhejiang Yongjia, 35kV user substation for a toy production base
- Shanxi Changzhi, farm substation (10kV)
- Zhejiang Shidarui Electric Vehicle, 3.45MWp distributed PV
- Changxing Bingfeng Technology, 4MWp distributed PV
- Zhejiang Dongyu Electric, 2.1MW distributed PV
FAQ
Q1: What is a Self-Powered Numerical Protection Relay?
It is a microprocessor protection relay that gets its operating power from the circuit's own current transformer, so it needs no DC panel or UPS.
Q2: Where is the NR-321 used?
In box-type substations, ring cabinets and small switchgear, in breaker cabinets or load-break-switch-plus-fuse cabinets.
Q3: Can it be installed in a low, wide door cut-out?
Yes. The NR-321 is the horizontal model, with a 153 × 78 mm front panel and a 148 × 72 mm cut-out. Its depth is 120 mm.
Q4: When do I choose the NR-320 instead?
When your cut-out is tall and narrow. The NR-320 is the vertical version, 75 × 153 mm with a 72 × 148 mm cut-out. The functions are the same.
Q5: What protection functions does it provide?
Two-stage definite-time overcurrent, inverse-time overcurrent, definite-time and inverse-time zero-sequence overcurrent, external-contact trip and high-current blocking trip.
Q6: Can protection thresholds / digital I/O be configured or customized?
Functions are switched in or out by menu. Rated values and digital I/O are customized in hardware, so state them before ordering. They cannot be changed by the user later.
Q7: Does it work next to fuses?
Yes. The high-current blocking trip is intended for use with various fuses and removes the protection dead zone in distribution systems.
Q8: Is the menu available in English?
Yes. The LCD interface is available in English.
Q9: What information is required for a quote?
System frequency, secondary rated current, operating voltage (DC24V or DC220V) and communication interface. Mention the cabinet type and cut-out orientation as well.
Q10: Do you provide OEM/ODM, drawings and testing support?
We provide OEM/ODM, project integration, technical support and after-sales service, including custom exteriors on large orders. Please ask our engineers for the drawings you need.
Get a Quote

Planning a cabinet with a landscape door cut-out? Send your system frequency, CT secondary current, operating voltage and communication needs. Our engineers will confirm the Self-Powered Numerical Protection Relay NR-321 configuration and reply with a quotation.
Hot Tags: self-powered numerical protection relay nr-321, China self-powered numerical protection relay nr-321 manufacturers, suppliers, factory