NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of ct-powered numerical protection relay nr-320 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.
Overview

The CT-Powered Numerical Protection Relay NR-320 is a self-powered protection and control device developed for ring main units (RMUs), box-type substations and small switchgear. It takes its operating power from the current transformer (CT) in the primary circuit. Switchgear builders therefore do not need to add a DC panel or UPS just to keep the protection running.
The relay can be installed in a circuit-breaker cabinet or in a load-break-switch-plus-fuse cabinet. It provides phase overcurrent protection and zero-sequence (earth-fault) overcurrent protection, with several operating curves to choose from. It can also trip through an external contact. The same unit protects busbars, lines, distribution transformers, motors and capacitors.
The device runs on very low power, so protection starts quickly under any condition. Its start-up power is only 0.2 VA. That also removes the "dead zone" problem in fuse-coordinated distribution protection, through its high-current blocking trip function.
NR-320 is built for vertical panel mounting and NR-321 is the same relay in a horizontal layout. Both measure 120 mm in depth and use a compact 148 × 72 mm panel cut-out, which suits the tight space of ring main units. Both come with an LCD user interface in English, so commissioning and daily operation are straightforward for overseas teams. They are made in our own factory, so rated current, trip voltage and communication interface are fixed to your order before production starts.

Key Features & Protection Functions
-

Protection functions
- Two-stage definite-time overcurrent protection
- Inverse-time overcurrent protection
- Definite-time zero-sequence overcurrent protection
- Inverse-time zero-sequence overcurrent protection
- Direct trip through an external contact
- High-current blocking trip
- Multiple IEC inverse-time curves, with every protection function enabled or disabled from the menu
-

Self-powered design
- Ultra-low power consumption, with fast and reliable start-up in all conditions
-
Optional CT power supply, with no DC panel or UPS needed
-
Passive trip output that drives the trip coil directly
Operation and monitoring
-
English-language LCD interface with multi-level menus
-
Large-capacity non-volatile memory storing 100 historical event records, kept after power loss
-
Static and dynamic self-checking, with online monitoring of every part of the device
-
High-precision components and proven manufacturing processes for long service life
-

Communication
- Front-panel RS-232 port for commissioning
-
Optional rear RS-485 bus port
-
Open communication protocol provided to the user, for easy SCADA integration
Installation
-
Compact housing, only 120 mm deep, for the tight space in ring main units
- Vertical (NR-320) and horizontal (NR-321) versions with a matching panel cut-out for each
Technical Specifications
|
Parameter |
Specification |
|
Model |
NR-320 (vertical mounting) / NR-321 (horizontal mounting) |
|
Auxiliary power supply |
DC 20 V – 100 V, or DC 220 V |
|
Rated current |
5 A or 1 A (customizable) |
|
Rated frequency |
50 Hz |
|
Trip output |
DC 24 V or DC 220 V |
|
CT-power start-up power |
0.2 VA |
|
Phase protection |
Two-stage definite-time overcurrent; inverse-time overcurrent |
|
Earth-fault protection |
Definite-time and inverse-time zero-sequence overcurrent |
|
Other trip functions |
External contact trip; high-current blocking trip; passive trip output |
|
Event records |
100 historical events, non-volatile |
|
Display |
LCD, English interface available |
|
Communication |
RS-232 front port (commissioning); RS-485 rear port (optional) |
|
Operating temperature |
−30 °C to +55 °C |
|
Relative humidity |
≤ 95 %, non-condensing |
|
Atmospheric pressure |
80 – 110 kPa |
Dimensions and panel cut-out
|
Item |
NR-320 (vertical) |
NR-321 (horizontal) |
|
Front panel (W × H) |
75 mm × 153 mm |
153 mm × 78 mm |
|
Body length / height |
147 mm (height) |
147 mm (width) |
|
Depth |
120 mm |
120 mm |
|
Panel cut-out (W × H) |
72.00 mm × 148.00 mm (+0.2 / 0) |
148.00 mm × 72.00 mm (+0.2 / 0) |
Operating environment: the air around the device must not contain acid, alkali, corrosive or explosive substances, and the installation must meet lightning, rain and snow protection requirements.
CT power supply requirements
|
Primary current |
CT secondary output |
|
10 % of CT rated current |
≥ 12 V |
|
50 % of CT rated current |
≥ 25 V |
|
100 % – 200 % of CT rated current |
25 V ≤ output < 30 V |
|
Above 100 % of CT rated current |
Open-circuit voltage < 40 V |
The power CT normally uses a measuring winding. It has no accuracy requirement, but its output capacity must cover the device's 0.2 VA start-up power.
Applications
NAHO's product range covers a wider variety of scenarios than most relay suppliers. The NR-320 is built for compact distribution equipment where a DC supply is hard to provide.

-
Substations
Ring main units, box-type substations and small switchgear. The relay fits breaker cabinets and load-break-switch-plus-fuse cabinets. It protects busbars, lines and distribution transformers. -
Hydropower
Compact distribution cabinets in hydropower plants and their auxiliary systems. A self-powered relay removes the need for extra DC equipment in small cabinets.

-
Distributed PV
Box-type substations and compact switchgear at distributed PV sites. NAHO has supplied PV projects across Anhui, Jiangsu, Zhejiang, Shandong and Hubei, with a single project of up to 10.96606 MW. -
Industrial & Mining
Distribution rooms in factories and mines. The relay protects lines, distribution transformers, motors and capacitors in small switchgear.

-
Rail & Transportation
Compact switchgear for transport infrastructure. NAHO is a drafting unit of NB/T 11483-2024 on relay protection for urban rail AC power supply systems.
How It Works
Signal Acquisition And Self-Powering
The CT measures the primary current and also powers the relay. At 10 % of rated primary current the CT already delivers 12 V or more, so the device wakes up even at light load.
Protection Logic
The relay compares phase current and zero-sequence current with the thresholds you set. The curve can be definite-time or an IEC inverse-time curve.
Fault Judgment
The relay checks which function has operated and for how long. A high-current blocking trip handles fault currents that a fuse should interrupt, which helps with fuse coordination.
Trip Command
The passive trip output drives the trip coil directly, at DC 24 V or DC 220 V. The relay can also trip through an external contact. The event is saved to memory and can be sent through RS-485.
Why Choose NAHO - Custom Engineering Capability

Many suppliers say they can customize. Here is what that means at NAHO, with facts you can check.
-
We have customized across many different scenarios.
We have delivered custom solutions for 144+ projects across substations, mines, PV plants, hydropower and rail. Few of them are the same. -
We cover the full range of voltage levels.
Our project record runs from 10 kV and 35 kV through 66 kV to 110 kV. -
We have been doing this for over 30 years.
The company began in 1992 and has focused on power automation since then. Our engineering team has been shaped by thousands of different customer specifications. -
Rated current and digital I/O are built to your requirement.
Rated current is 5 A or 1 A. Digital I/O is also customized at the hardware level, so tell us your requirements before ordering. The hardware is made to that specification. The customer cannot reconfigure it afterward, which keeps the product matched to your panel. -
Operating voltage and trip voltage are set at order.
Choose auxiliary supply of DC 20–100 V or DC 220 V and trip output of DC 24 V or DC 220 V. -
We offer OEM/ODM, project integration, technical support and after-sales service.
Appearance customization is available for large volumes, because custom housing tooling is costly. -
Every unit passes a defined factory process.
SMT placement with AOI inspection, wave soldering, program burn-in, a 72-hour aging test, withstand-voltage and short-circuit checks, a final inspection including time synchronization within 2 seconds, and two warehouse inspections. -
Warranty: 2 years from the date of arrival.
Certifications & Standards




Company certifications and test reports
- ISO 9001 quality management system
- CCC certification
- CE certification
- IEC 60255 / IEC 61850 type test reports
- KETOP Laboratory type test report
- State Grid qualified supplier (since 2018)
- All NAHO products pass type tests at the National Relay Protection and Automation Equipment Quality Inspection Center (KETOP Laboratory) and IEC-TC95 international standard testing
Standards NAHO has helped draft
- National standard: General technical requirements for standardized relay protection devices of 35 kV and below
- NB/T 11054-2023, Technical specification for anti-islanding protection devices
-
NB/T 11483-2024, Technical specification for relay protection of urban rail transit AC power supply systems
-
NB/T 11480-2024, Technical specification for environmental control systems of outdoor control cabinets in smart substations
Company recognition
National High-Tech Enterprise, National "Specialized, Refined, Distinctive and Innovative" enterprise (2023), 70+ patents and software copyrights, and a member of the China Electrical Equipment Industry Association relay protection branch since 2006.
Project References

NAHO company track record (company-level projects, not all with NR-320):
- 16th Asian Games (2010), Haixinsha Square opening ceremony power supply protection
- Three Gorges Yunyang reservoir area project
- Inner Mongolia wind farm
- Ningbo–Taizhou–Wenzhou high-speed railway
- 35 kV Yongci 15.6 MW distributed PV project
- Zhejiang Liyi Precision Manufacturing 10.96606 MW distributed PV project
- 35 kV substations for mining, steel, chemical and food-processing plants in Shanxi, Inner Mongolia, Xinjiang, Gansu and Shandong
- 10 kV distribution projects in coal mines, water treatment, cement and heating plants
FAQ
Q1: What is a CT-powered numerical protection relay?
It is a digital protection relay that takes its operating power from the current transformer on the protected circuit. It needs no DC panel or UPS. NR-320 is one such relay.
Q2: Where is the NR-320 used?
In ring main units, box-type substations and small switchgear. It can be mounted in a circuit-breaker cabinet or a load-break-switch-plus-fuse cabinet.
Q3: Can this device be used for motor, capacitor or transformer protection?
Yes. It can protect busbars, lines, distribution transformers, motors and capacitors, using its overcurrent and zero-sequence overcurrent functions.
Q4: What protection functions does it provide?
Two-stage definite-time overcurrent, inverse-time overcurrent, definite-time zero-sequence overcurrent, inverse-time zero-sequence overcurrent, external contact trip and high-current blocking trip.
Q5: Can protection thresholds and digital I/O be configured or customized?
Protection functions are switched on or off from the menu. Rated current and digital I/O are customized in hardware, so state your requirements before ordering. They cannot be changed by the customer after delivery.
Q6: What information is required for a quote or selection?
System frequency, secondary rated current (5 A or 1 A), operating voltage (DC 24 V or DC 220 V), communication interface, and the CT details for self-powering.
Q7: Do you provide OEM/ODM customization?
Yes. We offer OEM/ODM, project integration, technical support and after-sales service. Appearance customization is available for large orders.
Q8: What is the difference between NR-320 and NR-321?
They share the same functions. NR-320 is for vertical mounting and NR-321 for horizontal mounting.
Q9: What does the power CT need to provide?
Output of 12 V or more at 10 % of rated primary current and 25 V or more at 50 %. It must cover the relay's 0.2 VA start-up power.
Q10: Can you provide technical drawings, wiring diagrams and testing support?
Yes. We supply outline and cut-out drawings for both models, plus wiring diagrams. Our engineers support commissioning, and the device carries a 2-year warranty from arrival.
Q11: What size is the NR-320 and what cut-out does it need?
NR-320 has a 75 × 153 mm front panel and is 120 mm deep. It needs a 72 × 148 mm cut-out. NR-321 has a 153 × 78 mm front panel, is also 120 mm deep, and needs a 148 × 72 mm cut-out.
Q12: Is the display available in English?
Yes. The LCD interface is available in English, with multi-level menus for settings and event records.
Get a Quote

Tell us your application, rated current, operating voltage and communication needs. Our engineers will reply with a selection and quotation.
Hot Tags: ct-powered numerical protection relay nr-320, China ct-powered numerical protection relay nr-320 manufacturers, suppliers, factory