VT Protection and Monitoring Device NR-623A

VT Protection and Monitoring Device NR-623A

Custom-engineered VT protection and monitoring device for 10kV and below VT cabinets, tailored to your grid code and panel layout.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of vt protection and monitoring device nr-623a in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

NH12-2

 

The VT Protection and Monitoring Device NR-623A is a numerical protection and control relay for the voltage transformer (VT) cabinet. It monitors one set of VT signals on a busbar and protects against abnormal voltage conditions. It belongs to the NR-620 series, which is designed for 10kV and below small-current grounding systems.

In a VT cabinet, the relay has to do two jobs at once. It watches the bus voltage continuously, and it reacts when that voltage leaves its normal range. NR-623A does both from one unit. It measures three-phase voltage plus zero-sequence voltage (U0). It applies overvoltage, undervoltage and zero-sequence overvoltage protection, with a choice between alarm and trip. It also provides busbar insulation monitoring and a VT wire-break self-check, so a faulty secondary circuit does not go unnoticed. Fault recording captures the event for later analysis.

 

NR-623A is made for cabinets with a single VT group. If your cabinet needs monitoring and paralleling of two VT groups, the NR-623 model in the same series is the matching variant.

Because NAHO designs and builds this relay in its own factory, the rated values and digital I/O can be defined to suit your cabinet before production. That suits switchgear builders, system integrators and distributors who supply VT cabinets with non-standard requirements.

product-1200-900

 

 

Key Features & Protection Functions

  • product-5712-3213

    Voltage Protection

    • Overvoltage protection, configurable for alarm or trip

    • Undervoltage protection, configurable for alarm or trip

    • Zero-sequence overvoltage protection, configurable for alarm or trip

  • product-5712-4284

    Monitoring & Self-Supervision

    • Three-phase voltage plus U0 measurement channels
    • Busbar insulation monitoring

    • VT wire-break self-check

     

    Recording & Diagnostics

    • Fault recording for post-event analysis

  • product-1265-949

    Interfaces & Integration

    • 12 digital inputs, with user-defined input functions
    • 4 dry-contact outputs

    • RS-485 / Ethernet communication (Ethernet optional)

    • Modbus, IEC 60870-5-101 and IEC 60870-5-103 protocols

     

    Hardware & Power Supply

    • Wide-range auxiliary supply: AC/DC 85–265V or DC48V

    • Rated current 5A or 1A (customized at order)

     

 

 

Technical Specifications

 

Parameter

NR-623A

Product series

NR-620 series

Application

VT cabinet, monitoring and protection of one VT group

System voltage level

10kV and below, small-current grounding system

Voltage measurement channels

3-phase + U0

Digital inputs

12

Digital outputs

4 dry contacts

Communication ports

RS-485 / Ethernet (optional)

Communication protocols

Modbus / IEC 101 / IEC 103

Digital input definition

User-defined

Overvoltage protection

Alarm or trip

Undervoltage protection

Alarm or trip

Zero-sequence overvoltage protection

Alarm or trip

Busbar insulation monitoring

Yes

VT wire-break self-check

Yes

Fault recording

Yes

Auxiliary power supply

AC/DC 85–265V; DC48V

Rated voltage

100V

Rated frequency

50Hz

Rated current

5A; 1A (customized)

Operating temperature

-30°C to +55°C

Relative humidity

≤ 95%, non-condensing

Atmospheric pressure

80–110 kPa

Ambient conditions

No acid, alkali, corrosive or explosive substances in the surrounding air

Front panel size

149 mm × 188 mm

Rear size

138 mm × 158 mm

Panel cutout

139 mm ± 0.5 × 159 mm ± 0.5

Overall depth

108 mm

 

Rated values and digital I/O can be customized. Please state your requirements before ordering.

 

Applications

 

 

NR-623A is made for VT cabinets, but the NAHO product range spans five scenario groups. Here is where VT monitoring and protection fits in each.

 

product-1264-711
  • Substations
    Bus VT cabinets in 10kV and below distribution substations, where voltage monitoring and insulation supervision are needed on the busbar.

  • Hydropower
    Medium-voltage busbars at hydropower stations, where bus voltage must be watched and abnormal conditions alarmed or tripped.

product-1672-940
  • Distributed PV
    Grid-connection and distribution rooms of distributed PV plants, where the medium-voltage bus needs voltage and zero-sequence monitoring.

  • Industrial & Mining
    Plant and mine distribution rooms with 10kV or 6kV systems, where VT cabinets sit on the incoming and sectionalized busbars.

product-1246-701
  • Rail & Transportation
    Power supply and distribution rooms for rail and transportation projects, where a compact VT relay saves panel space.

 

 

How It Works

 

 

Signal Acquisition

The device takes the secondary voltage of the VT, three phases plus zero-sequence voltage U0, through its voltage measurement channels. Digital inputs bring in switch status from the cabinet.

Protection Logic

The measured values are compared with the overvoltage, undervoltage and zero-sequence overvoltage settings. At the same time, busbar insulation monitoring and the VT wire-break self-check run continuously.

Fault Judgment

When a value leaves its allowed range, or a VT circuit problem is found, the device judges the condition. Each voltage function can be set to alarm only or to trip. Fault recording stores the event.

Trip / Alarm Command

The device issues its command through its dry-contact outputs. It also reports status and events to the supervisory system through RS-485 or Ethernet using Modbus, IEC 101 or IEC 103.

 

 

Why Choose NAHO: Custom Engineering Capability

 

product-1267-1027

We win projects because we can build what standard catalogs do not offer. Each promise below comes with something you can check.

  • We have customized for many different sites.
    NAHO has delivered customized solutions for 144+ different projects, including substations, hydropower, mining, photovoltaic and rail transit. These projects cover 110kV, 66kV, 35kV and 10kV levels.

  • We set rated values and digital I/O to your drawing.
    For every NAHO product, the rated values and digital I/O can be customized. You state them in the order remarks, and our engineers do the hardware customization at the factory. NR-623A also lets you define the function of its 12 digital inputs.

  • We build the hardware, so we can change it.
    Hardware customization is done in our own production line in Yueqing, Zhejiang. The line includes SMT placement with AOI inspection, wave soldering, CPU program burn-in and a full assembly stage. Because the customization is made in hardware, please confirm your I/O requirements before ordering; you cannot reconfigure them later on site.

  • We tested the device before it reaches your cabinet.
    Each unit goes through initial debugging and a 72-hour aging test with 24V, 48V or 220V power. It then goes through component life checks, withstand voltage test and short-circuit check. Final inspection includes manual re-tuning and a time-synchronization check within 2 seconds.

  • We can do appearance customization for large orders.
    Housing customization is possible for high-volume orders, because the mold development cost needs volume to justify.

  • We offer OEM/ODM, integration and after-sales.
    Our service covers OEM/ODM customization, project integration, technical support and after-sales service. Warranty is 2 years, counted from the arrival of the goods.

  • We have 30+ years in power automation.
    The company started in 1992, and in 2003 it focused on power intelligence and microcomputer protection. It holds 70+ patents and software copyrights.

 

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711

Testing

  • All NAHO products pass type tests at the KETOP Laboratory, the national relay protection and automation equipment quality inspection and testing center
  • IEC-TC95 international standard testing

 

Certificates available on request (English versions)

  • ISO 9001 quality management system
  • CCC
  • CE
  • IEC 60255 / IEC 61850 related type test reports
  • KETOP laboratory type test reports
  • State Grid qualified supplier certificate (qualified since 2018)

 

Standards participation

  • Drafting participant of the national standard for general technical requirements of standardized relay protection devices for 35kV and below
  • NB/T 11054-2023, Technical specification for anti-islanding protection devices
  • NB/T 11483-2024, Technical specification for relay protection of AC power supply systems in urban rail transit
  • NB/T 11480-2024, Technical specification for environmental control systems of outdoor control cabinets in smart substations

 

Company recognition
National High-tech Enterprise, National Specialized and Innovative "Little Giant" enterprise (2023), National Torch Program industrialization project unit, and member of the China Electrical Equipment Industry Association relay protection and automation branch (since 2006).

 

 

Project References

 

 

NAHO has delivered 144+ substation projects and many distributed PV projects across China. Here is a selection that shows the range of sites and voltage levels.

 

Project

Voltage level / type

Xinjiang Kashgar Tarlega 110kV construction substation

110kV

Gansu Zhangye Shandan Tieqi Cement 110kV substation

110kV

Jilin Yanji heat source plant main step-down 66kV-6kV distribution

66kV-6kV

Jilin Haigou Gold Mine 66kV distribution room renovation

66kV

Shanxi Changzhi Yantuo 35kV substation

35kV

Inner Mongolia Baotou Furong 35kV substation expansion

35kV

Qinghai Golmud Salt Lake 35kV substation

35kV

Ningbo Yongci 35kV 15.6MW distributed PV project

35kV

Hangzhou Wanma Muying apartments distribution

35kV

Xining Opera House high and low voltage distribution rooms

35kV

Hubei Shennongjia Shennong Hotel distribution station

10kV

Ordos Jingangwan International Racing Circuit

10kV

Zhejiang Liyi Precision 10.96606 MW distributed PV project

Distributed PV

Anhui Tonghua Auto Parts 4.5MW rooftop PV project

Distributed PV

 

Landmark projects: the power supply protection and distribution project at Haixinsha Square for the opening ceremony of the 16th Asian Games (2010), the Three Gorges Yunyang reservoir area project, Inner Mongolia wind farm, and the Yong-Tai-Wen high-speed railway.

Our project footprint spans Xinjiang, Gansu, Inner Mongolia, Shandong, Shanxi, Shaanxi, Jiangxi, Guizhou, Yunnan, Hubei, Sichuan and other provinces.

 

 

FAQ

 

Q1: What is a VT protection and monitoring device?

It is a numerical relay installed in the VT cabinet. It measures the busbar voltage through the voltage transformer, protects against abnormal voltage, and monitors the condition of the busbar and the VT circuit.

Q2: Where is the VT Protection and Monitoring Device NR-623A used?

It is used in VT cabinets of 10kV and below systems. Typical sites are substations, hydropower stations, distributed PV plants, industrial and mining plants, and rail and transportation power rooms.

Q3: Can this device be used for a VT cabinet with two VT groups?

NR-623A is designed for monitoring and protecting one VT group. For two VT groups with paralleling, the NR-623 in the same NR-620 series is the matching model. Tell us your cabinet layout and we will confirm the right one.

Q4: What protection functions does it provide?

Overvoltage, undervoltage and zero-sequence overvoltage protection, each set for alarm or trip. It also provides busbar insulation monitoring, VT wire-break self-check and fault recording.

Q5: Can protection thresholds / digital I/O be configured or customized?

Rated values and digital I/O can be customized, but they must be stated in the order remarks. The hardware is customized at the factory, so customers cannot reconfigure it afterwards. The functions of the 12 digital inputs are user-defined. Overvoltage, undervoltage and zero-sequence overvoltage can each be set to alarm or trip.

Q6: What communication does it support?

RS-485 and Ethernet (Ethernet optional), with Modbus, IEC 101 and IEC 103 protocols.

Q7: What information is required for a quote or selection?

Please send us: the system voltage level, rated voltage and rated current (5A or 1A), auxiliary power supply type, the number of VT groups in the cabinet, required digital input and output functions, communication port and protocol, panel cutout size, and the quantity.

Q8: Do you provide OEM/ODM customization?

Yes. We offer OEM/ODM customization, project integration, technical support and after-sales service. Appearance customization is possible for high-volume orders because of the mold development cost.

Q9: Can you provide technical drawings, wiring diagrams and testing support?

Yes. Our service covers technical support and after-sales service for your projects. Dimension data, including the 139 mm × 159 mm panel cutout, is listed in the specification table. Send us your project requirements and we will tell you what documents apply.

Q10: What is the minimum order quantity and warranty?

The MOQ for the NR-620 series is 20 units. The warranty is 2 years, counted from the arrival of the goods.

 

Get a Quote (page bottom + fixed floating button)

 

product-1269-952

Tell us your VT cabinet. We will engineer the relay around it.

Send your voltage level, VT group count, I/O list and panel size. Our engineers will reply with a selection suggestion and quotation.

Get a Quote

 

Hot Tags: vt protection and monitoring device nr-623a, China vt protection and monitoring device nr-623a manufacturers, suppliers, factory