Feeder Arc Flash Protection Device NR-ARC-500

Arc-light-based protection for 35kV and below small-current grounding systems, with 16 arc inputs and 13 trip outputs, built to your panel layout.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of feeder arc flash protection device nr-arc-500 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

product-1-1

 

The NR-ARC-500 is a feeder arc flash protection device engineered and manufactured by NAHO for switching stations and customer substations in small-current grounding systems rated 35kV and below. It uses the arc light signal produced by a fault in primary equipment as its main criterion, with electrical quantities as the auxiliary criterion. When a fault occurs, the device trips through its output relays to isolate the faulted equipment.

Arc faults release enormous energy in a very short time. The NR-ARC-500 detects and isolates arc faults within 10–20 ms. That limits equipment damage, protects personnel and keeps the power supply stable and reliable.

 

With 16 arc light inputs, four sets of three-phase current inputs and 13 trip outputs, one device covers multi-cabinet arc protection. It communicates over standard RS-485 (Modbus, IEC 101, IEC 103) and B-code time synchronization. Optional dual Ethernet ports add IEC 104 and Modbus-TCP.

The NR-ARC-500 is available in standard and fully customized configurations. As a factory with more than 30 years of manufacturing experience, NAHO can adapt rated current, communication options and enclosure design to your project instead of asking you to adapt to a catalog.

product-5712-3213

 

 

Key Features & Protection Functions

  • product-1200-800

    Protection Logic

    • Arc light signal as the main criterion for fast fault identification
    • Electrical quantities as the auxiliary criterion, so the arc signal is confirmed against the system's electrical behavior
    • Fast tripping through output relays to isolate the faulted equipment
    • Detects and isolates arc faults within 10–20 ms
  • product-5712-4284

    Measurement Functions

    • Four sets of three-phase current inputs (Ia1–Ic4)
    • 16 arc light inputs (ARC1–ARC16)

    • Rated current 5A or 1A (customized to your CT configuration)

     

    Communication Functions

    • 2 × RS-485 as standard, supporting Modbus, IEC 101 and IEC 103
    • 1 × B-code time synchronization input (differential) as standard

    • Optional 2 × 10/100M self-adaptive Ethernet ports supporting IEC 104 and Modbus-TCP

  • product-1200-900

    Monitoring Functions

    • 13 trip outputs for flexible tripping of multiple breakers
    • Power-loss alarm output

    • Wide-range auxiliary supply, AC/DC 85–220V

 

Selection note: The 16 arc inputs and 13 trip outputs let a single NR-ARC-500 cover several feeder or switchgear compartments. Tell us your cabinet count and tripping scheme, and we will confirm the configuration before you order.

 

 

Technical Specifications

 

Parameter

Specification

Applicable Scope

Small-current grounding systems, 35kV and below; switching stations and customer substations

Main Criterion

Arc light signal

Auxiliary Criterion

Electrical quantities

Arc Fault Detection & Isolation

Within 10–20 ms

Auxiliary Power Supply

AC/DC 85–220V

Rated Current

5A or 1A (customized)

Rated Frequency

50Hz

Current Inputs

4 sets of three-phase current inputs

Arc Light Inputs

16 channels (ARC1–ARC16)

Trip Outputs

13 channels

Alarm Output

Power-loss alarm

Communication Ports

2 × RS-485 (standard); 2 × 10/100M self-adaptive Ethernet (optional)

Communication Protocols

Modbus / IEC 101 / IEC 103 (RS-485); IEC 104 / Modbus-TCP (Ethernet, optional)

Time Synchronization

1 × B-code (differential)

Operating Temperature

-10℃ ~ +55℃

Relative Humidity

≤95%, non-condensing

Atmospheric Pressure

80–110kPa

Environmental Conditions

Ambient air free of acid, alkali corrosives and explosive substances; lightning, rain and snow protection required at site

Dimensions

155mm (W) × 230mm (H) × 195mm (D)

Panel Cutout

139mm (W) × 212mm (H)

Compliance

Type-tested by the KETOP Laboratory (National Relay Protection & Automation Equipment Quality Inspection Center); IEC-TC95 international standard tested

 

Applications

 

product-1264-711

Switching stations

Arc fault protection for the medium-voltage switchgear of switching stations in 35kV and below small-current grounding systems.

product-1672-940

Customer substations

Protection for the medium-voltage switchgear of customer-owned substations, where an arc fault can cause costly downtime and equipment damage.

product-1246-701

Industrial & mining distribution systems

Arc flash protection for plant distribution rooms in industries such as mining, steel, chemicals and building materials. A single unit with 16 arc inputs can cover several cabinets.

 

 

How It Works

 

Arc Light Acquisition

When an arc fault occurs in primary equipment, the arc light signal is received through the device's arc inputs (up to 16 channels).

Auxiliary Criterion Check

The device evaluates the electrical quantities from its three-phase current inputs as the auxiliary criterion. This supports reliable identification of a genuine fault.

Fault Judgment

The arc light criterion and the auxiliary criterion are combined to decide quickly whether a fault has occurred and which area is affected.

Trip Command

The device operates its trip outputs (up to 13 channels) to clear the faulted equipment. Arc faults are detected and isolated within 10–20 ms, limiting damage and protecting personnel.

 

 

Why Choose NAHO: Built Around Your Project, Not Our Catalog

 

product-1267-1027

NAHO is a manufacturer, not a trading company. We design, build and test our protection devices in our own factory in Yueqing, Zhejiang. Our foundation is more than 30 years of power automation experience, dating back to 1992.

 

Custom engineering you can verify:

  • Rated current on request. The NR-ARC-500 is supplied with 5A or 1A current inputs to match your CT configuration.
  • Communication options. RS-485 with Modbus / IEC 101 / IEC 103 is standard. Dual Ethernet ports with IEC 104 and Modbus-TCP can be added.
  • Custom enclosure and panel design. We accept large-volume custom appearance requirements. Our tooling investment is justified once your order volume supports it.
  • OEM/ODM, project integration, technical support and after-sales service across the full project cycle.
  • Proven range. We have delivered 144+ projects from 110kV down to 10kV, across more than 11 provinces in China and in mining, steel, chemicals, construction, transportation and photovoltaics. The largest single PV project is 10.96606 MW.

 

Factory quality control on every device

  • SMT production line with AOI inspection
  • Wave soldering with visual inspection, touch-up and a second AOI inspection
  • CPU board program burning and assembly
  • Initial commissioning, then 72-hour aging under 24V / 48V / 220V power
  • Component life check, withstand-voltage test and short-circuit check
  • Final inspection: manual re-commissioning, appearance check (panel, rear cover, screws, printed text, lens) and device time synchronization within 2 seconds
  • Two warehouse inspections before shipment

product-900-643

 

2-year warranty from the date of delivery.

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711
  • Type tests: All NAHO product series are type-tested by the KETOP Laboratory (National Relay Protection & Automation Equipment Quality Inspection Center)
  • International standard: Tested to IEC-TC95 international standards
  • National standard drafting: Participated in drafting the national standard for 35kV and below standardized protection devices (2019 and 2021)
  • Industry standards drafting:

     ○ NB/T 11054-2023, Technical Specification for Anti-islanding Protection Devices

     ○ NB/T 11483-2024, Technical Specification for Relay Protection of Urban Rail Transit AC Power Supply Systems

     ○ NB/T 11480-2024, Technical Specification for Environmental Control Systems of Outdoor Control Cabinets in Smart Substations

  • State Grid qualified supplier (since 2018)
  • National High-tech Enterprise and National "Specialized, Refined, Distinctive and Innovative" (SRDI) Enterprise (2023)
  • 70+ patents and software copyrights
  • Member and council unit of the China Electrical Equipment Industry Association, Relay Protection & Automation Equipment Branch (since 2006)

 

 

Case Studies / Project References

 

NAHO has completed 144+ projects across 110kV, 66kV, 35kV and 10kV, and the list below is a representative selection of them.

 

product-1200-675

Landmark projects: 

  • Power supply protection and distribution for the Haixinsha Square Opening Ceremony, 16th Asian Games (2010)
  • Three Gorges Yunyang Reservoir Area project

 

 

Representative references

 

 

Project

Voltage Level

Industry

Gansu Zhangye Shandan cement plant 110kV substation

110kV

Building materials

Xinjiang Hash 110kV construction substation

110kV

Construction / infrastructure

Shanxi Lanxian coking waste-heat power generation project

66kV

Coking / power

Jilin Haigou gold mine 66kV distribution room renovation

66kV

Mining

Hebei Chengde mining company 35kV substation

35kV

Mining

Inner Mongolia Baotou Furong 35kV substation expansion

35kV

Industrial

Anhui aluminum company 35kV distribution project

35kV

Metallurgy

Gansu Jiuquan mining company 35kV substation

35kV

Mining

Qinghai Golmud Salt Lake 35kV substation

35kV

Chemical

Xinjiang Hami highway toll station 35kV distribution project

35kV

Transportation

Shandong Linyi fuel additive company 35kV distribution project

35kV

Chemical

Hubei Shennongjia hotel distribution station

10kV

Commercial building

Anda wastewater treatment plant distribution room

10kV

Environmental

Jilin Huadian Baoyuan coal mine

10kV

Mining

 

Photovoltaic references include a 10.96606 MW distributed PV project in Zhejiang and a 4.5 MW rooftop PV project in Anhui.

 

 

FAQ

 

Q1: What is a feeder arc flash protection device?

It is a protection device that detects the arc light produced by an electrical arc fault in switchgear and trips the relevant breakers to clear the fault. The NR-ARC-500 uses the arc light signal as its main criterion and electrical quantities as the auxiliary criterion.

Q2: Where is the NR-ARC-500 used?

It is used in switching stations and customer substations in small-current grounding systems rated 35kV and below, including plant distribution rooms in industries such as mining, steel and chemicals.

Q3: How fast does it clear an arc fault?

The NR-ARC-500 detects and isolates arc faults within 10–20 ms. This limits equipment damage and protects personnel.

Q4: How does it protect the system?

It uses a two-criterion logic. The arc light signal is the main criterion and the electrical quantities from the current inputs are the auxiliary criterion. When a fault is identified, the device trips through its output relays.

Q5: How many arc inputs and trip outputs does it have?

The device provides 16 arc light inputs (ARC1–ARC16), four sets of three-phase current inputs and 13 trip outputs. It also has a power-loss alarm output.

Q6: Which communication protocols are supported?

Two RS-485 ports support Modbus, IEC 101 and IEC 103 as standard, and a B-code time synchronization input is included. Two optional 10/100M Ethernet ports add IEC 104 and Modbus-TCP.

Q7: Can the rated current be customized?

Yes. The rated current can be supplied as 5A or 1A to match your CT configuration. The Ethernet ports are also an optional configuration.

Q8: Do you provide OEM/ODM customization?

Yes. NAHO offers OEM/ODM customization, project integration, technical support and after-sales service. We accept custom enclosure and panel design for large-volume orders, because the tooling cost is justified at that scale.

Q9: What information do you need to quote or select a model?

Please send us your project location, system voltage, the number of cabinets or arc points, trip output requirements, communication needs and quantity. See the "Get a Quote" section below for the full list.

Q10: What warranty do you provide?

We provide a 2-year warranty counted from the date of delivery.

 

Get a Quote

 

product-1269-952

Send us the following information and our engineers will reply with a selection and quotation within 24 hours:

  • Project name and location
  • System voltage and frequency
  • Application type (switching station / customer substation / industrial or mining distribution)
  • Number of cabinets or arc points to be protected
  • Number of trip outputs required
  • Rated current (5A or 1A)
  • Communication requirements (RS-485 protocols; optional Ethernet with IEC 104 / Modbus-TCP)
  • Quantity
  • Customization requirements (enclosure, panel layout, special configuration)

 

Request a Quote

 

Hot Tags: feeder arc flash protection device nr-arc-500, China feeder arc flash protection device nr-arc-500 manufacturers, suppliers, factory