Transformer High Voltage Backup Protection Relay NR-500TB2

Transformer High Voltage Backup Protection Relay NR-500TB2

Factory-built backup protection relay for the medium- and low-voltage sides of 110kV-and-below main transformers, with customizable ratings.
Send Inquiry
Description

NAHO Electric Power Technology Co., Ltd. is one of the leading manufacturers and suppliers of transformer high voltage backup protection relay nr-500tb2 in China. With a professional team, we are committed to providing high quality customized service and OEM&ODM service for global customers. Please rest assured to wholesale bulk premium products at competitive price from our factory. Also, quotation is available.

 

Overview

 

 

NH26-2

 

NAHO (NRUICN) designs, manufactures and tests the NR-500TB3 transformer low voltage backup protection relay in our own factory in Yueqing, Zhejiang, where we have built power automation equipment since 1992. The NR-500TB3 is a microcomputer-based backup protection and measurement-control device for the medium- and low-voltage sides of main transformers in substations rated 110kV and below.

Its job is to back up the main protection. When a fault on the transformer's medium- or low-voltage side is not cleared in time, the NR-500TB3 detects it and trips, so the fault does not spread to the rest of the system. It combines time-limited instantaneous overcurrent, complex-voltage-blocked directional overcurrent, overload protection and busbar earth-fault alarm with PT/CT self-supervision, an integrated operation box and fault recording.

 

The NR-500TB3 belongs to the NR-500T transformer protection family. The NR-500TD3 and NR-500TD2 provide main protection for three-winding and two-winding transformers. The NR-500TB1 covers the 110kV-side backup, the NR-500TB2 covers the 35kV-side backup and measurement-control, and the NR-500TN covers non-electrical quantity protection. Because we manufacture the whole family ourselves, the NR-500TB3 is available in standard and customized

configurations, including rated current, rated voltage and auxiliary power supply.

product-1200-900

 

 

Key Features & Protection Functions

 

  • product-1200-800

    Protection Functions

    • Time-limited instantaneous overcurrent protection (ANSI 50/51)

    • Complex-voltage-blocked directional overcurrent protection, 2 time stages (Complex-voltage start for HV-side overcurrent (ANSI 51V)

    • Gap overcurrent protection (ANSI 50N/51N, gap zero-sequence current)

    • Overload protection (ANSI 51)

    • Busbar earth-fault alarm (ANSI 64)

  • product-5712-4284

    Measurement Functions

    • 6-phase + I0 current protection/measurement channel
    • 3-phase + U0 voltage measurement channel

    • 4–20mA DC analog signal acquisition

     

    Communication Functions

    • 1 × RS-485 port as standard
    • Optional configuration: 2 × RS-485 + 2 × Ethernet ports

  • product-1265-949

    Monitoring & Self-Supervision Functions

    • 16-way digital input; 14-way digital output

    • PT failure self-check; PT disconnection self-check; CT disconnection self-check

    • Integrated operation box

    • Operation circuit self-check (ANSI 74)

    • Fault recording

 

 

How the NR-500TB3 differs from the other backup models

 

 

Model

Typical position

Distinguishing functions

NR-500TB1

Main transformer 110kV-side backup

Gap overcurrent, zero-sequence overvoltage, zero-sequence-voltage-blocked directional zero-sequence overcurrent

NR-500TB2

Main transformer 35kV-side backup & measurement-control

Busbar earth-fault alarm, operation box

NR-500TB3

Main transformer medium- and low-voltage-side backup

Complex-voltage start for HV-side overcurrent, busbar earth-fault alarm, operation box

 

 

Technical Specifications

 

Parameter

Specification

Applicable Scope

Backup protection for the medium- and low-voltage sides of main transformers in substations rated 110kV and below

Current Protection/Measurement Channel

6-phase + I0

Voltage Measurement Channel

3-phase + U0

Digital Input

16-way

Digital Output

14-way

Communication Port

1 × RS-485 as standard; optional 2 × RS-485 + 2 × Ethernet

Protection Functions

Time-limited instantaneous overcurrent; complex-voltage-blocked directional overcurrent (2 time stages); complex-voltage start for HV-side overcurrent; overload; busbar earth-fault alarm

Self-Supervision

PT failure, PT disconnection, CT disconnection, operation circuit self-check

Other Functions

Operation box; fault recording

Auxiliary Power Supply

AC/DC 110V or AC/DC 220V; DC 48V

Rated Voltage

100V (400V customized)

Rated Frequency

50Hz

Rated Current

5A (1A customized)

DC Analog Signal Acquisition

4–20mA

Operating Temperature

-30℃ ~ +55℃

Relative Humidity

≤95%, non-condensing

Atmospheric Pressure

80–110kPa

Test Standard Atmospheric Condition

15℃ ~ 35℃, 45% ~ 75% RH, 86 ~ 106kPa

Installation Environment

The surrounding air must be free of conductive dust, corrosive gas and explosive substances, and the site must be protected from rain, snow and similar weather

Front Panel Dimensions

156mm (W) × 232mm (H)

Depth

171mm (body); 198mm including terminals

Rear View Dimensions

136mm (W) × 210mm (H)

Panel Cutout

approx. 137mm (W) × 211mm (H)

Type Testing

KETOP Laboratory type test; IEC-TC95 international standard testing

 

Applications

 

 

modular-1
  • Substation main transformer backup (110kV and below): backup protection on the medium- and low-voltage sides of main transformers, working with the NR-500TD main protection relays.

modular-2
  • Industrial user substations: main-transformer backup in the substations of metallurgy, mining, chemical and cement plants, where a transformer fault must not stall production.

modular-3
  • Substation upgrades and expansions: replacing or adding backup protection on existing main transformers, with the rated current, rated voltage and communication ports configured to match the project.

 

 

How It Works

 

Signal Acquisition

The relay samples the medium- and low-voltage-side currents (6-phase + I0) and voltages (3-phase + U0) from the CTs and PTs.

Protection Logic

It compares the sampled values against the set thresholds. Complex-voltage and directional elements decide whether an overcurrent is a real fault.

Fault Judgement

PT and CT self-checks confirm that the measurements are valid, so a broken CT or PT circuit does not cause a false operation.

Trip Command

If the fault persists beyond the set time stage, the relay trips the breaker through its operation box and records the event with fault recording.

 

 

Why Choose NAHO: Built Around Your Project, Not Our Catalog

product-1267-1027

We are the manufacturer, not a reseller. The NR-500TB3 is designed, assembled, aged and tested in our own factory, so the people who build it can adjust it for your project.

 

  • Customizable ratings you can verify on the datasheet. Rated current is 5A as standard and 1A on request. Rated voltage is 100V as standard and 400V on request. Auxiliary power can be AC/DC 110V, AC/DC 220V or DC 48V. Communication can be 1 × RS-485 or 2 × RS-485 + 2 × Ethernet.

  • 30+ years of power automation manufacturing. Our predecessor company was founded in 1992 in Yueqing Liushi.

  • Customization proven across 144+ projects. Our project record covers 110kV, 66kV, 35kV and 10kV voltage levels in substations, mines, steel, chemical, transport and distributed PV, across many provinces. Distributed PV projects reach up to 10.96606 MW.

  • OEM/ODM, project integration, technical support and after-sales service. Custom enclosure appearance is available for large-volume orders, because the tooling investment is justified once order volume supports it.

  • Every unit is tested before shipment. Production includes SMT with AOI inspection, a 72-hour aging test, withstand-voltage and short-circuit checks, and a final factory inspection.

 

Certifications & Standards

 

product-1221-1628
product-1268-1711
product-1267-1710
product-1268-1711
  • Type-tested at the KETOP Laboratory (National Relay Protection and Automation Equipment Quality Inspection and Testing Center)
  • Passed IEC-TC95 international standard testing
  • Drafting participant of the national standard for 35kV and below standardized relay protection devices (2019 and 2021)
  • Drafting participant of energy industry standards NB/T 11054-2023 (Technical Specification for Anti-islanding Protection Devices), NB/T 11483-2024 (Technical Specification for Relay Protection of AC Power Supply Systems for Urban Rail Transit) and NB/T 11480-2024 (Technical Specification for Environment Control Systems of Outdoor Control Cabinets in Smart Substations)
  • State Grid qualified supplier (since 2018)
  • National High-tech Enterprise; National "Specialized, Refined, Distinctive and Innovative" Enterprise (2023)
  • 70+ patents and software copyrights
  • Member and executive-council member unit of the Relay Protection and Automation Equipment Branch of the China Electrical Equipment Industry Association

 

Case Studies / Project References

 

 

NAHO has delivered 144+ power projects. A selection is shown below. These are company project references, not a list of NR-500TB3 installations.

 

Project

Voltage Level

Industry

Shandan Tieqi Cement 110kV Substation, Zhangye, Gansu

110kV

Cement

Chunlong 110kV Substation, Jinta County, Jiuquan, Gansu

110kV

Industrial

Hash Tarilega 110kV Construction Substation, Xinjiang

110kV

Construction power

Haigou Gold Mine 66kV Distribution Room Renovation, Jilin

66kV

Mining

Yanji Central Heating Plant 66kV–6kV Distribution, Jilin

66kV–6kV

Heating

Anshan Datongwan Industrial Zone 66kV Substation Renovation, Liaoning

66kV

Industrial

Baotou Furong 35kV Substation Expansion, Inner Mongolia

35kV

Industrial

Jinan Longshan Relay Pump Station 35kV Substation, Shandong

35kV

Water supply

Shanxi Datong Xing'ergou Coal Mine 35kV/6kV Substation

35kV/6kV

Mining

Tibet Dangdui 35kV Substation

35kV

Utility

Anhui Shengxin Aluminum 35kV Distribution Project

35kV

Metallurgy

Shanghai Hudong Heavy Machinery Donggou Plant 35kV–6.3kV Distribution

35kV–6.3kV

Machinery

 

Landmark projects

  • Power supply protection and distribution for the Haixinsha Square opening ceremony, 16th Asian Games (2010)

  • Three Gorges Yunyang Reservoir area project

 

 

FAQ

 

Q1: What is a transformer low voltage backup protection relay?

It is a protection device installed on a main transformer's low-voltage side, and on the medium-voltage side for three-winding transformers. It backs up the main protection and trips the breaker if a fault is not cleared in time.

Q2: Where is the NR-500TB3 used?

It is used in substations rated 110kV and below, on the medium- and low-voltage sides of main transformers. It is also used in industrial user substations such as mining, metallurgy and chemical plants.

Q3: Can the NR-500TB3 be used as the main protection of a transformer?

No. The NR-500TB3 is a backup protection device. For main protection, use the NR-500TD3 (three-winding) or NR-500TD2 (two-winding) in the same family.

Q4: What protection functions does the NR-500TB3 provide?

It provides time-limited instantaneous overcurrent, complex-voltage-blocked directional overcurrent with 2 time stages, complex-voltage start for HV-side overcurrent, overload protection and busbar earth-fault alarm. It also provides PT/CT self-checks, an operation box, operation circuit self-check and fault recording.

Q5: What is the difference between the NR-500TB1, NR-500TB2 and NR-500TB3?

The NR-500TB1 backs up the 110kV side and adds gap overcurrent and zero-sequence overvoltage. The NR-500TB2 backs up the 35kV side with measurement-control. The NR-500TB3 backs up the medium- and low-voltage sides and adds complex-voltage start for HV-side overcurrent.

Q6: Can the rated current, rated voltage or power supply be customized?

Yes. Rated current is 5A as standard and 1A on request. Rated voltage is 100V as standard and 400V on request. Auxiliary power is available as AC/DC 110V, AC/DC 220V or DC 48V.

Q7: What communication ports are available?

One RS-485 port comes as standard. You can also order 2 × RS-485 + 2 × Ethernet ports.

Q8: Do you provide OEM/ODM customization?

Yes. We are the manufacturer and offer OEM/ODM, project integration, technical support and after-sales service. Custom enclosure appearance is available for large-volume orders.

Q9: What is the minimum order quantity and warranty?

The MOQ is 10 units. The warranty is 2 years from the date of arrival.

Q10: What information do you need to quote?

See the list in the Get a Quote section below.

 

Get a Quote 

 

product-1269-952

Send us the following and we will reply within 24 hours:

  • Project name & location
  • System voltage & frequency
  • Transformer winding type (two-winding / three-winding) and the side to be protected
  • Application type (substation / industrial / mining / other)
  • Required protection functions
  • Rated current (5A / 1A) and rated voltage (100V / 400V)
  • Auxiliary power supply (AC/DC 110V / AC/DC 220V / DC 48V)
  • Communication port requirements
  • Quantity
  • Customization requirements

 

Request a Quote

 

Hot Tags: transformer high voltage backup protection relay nr-500tb2, China transformer high voltage backup protection relay nr-500tb2 manufacturers, suppliers, factory